Storm overflow register · Anglian Water

Billinghay sewage works: storm overflow spills 2025

Billinghay sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Billinghay Soke Dyke. In 2025 it recorded 48 spills totalling 400 hours, against 96 spills and 1,021 hours in 2024. By hours spilling, it ranks 54 of 419 Anglian Water works, where 1 spilled longest.

Works size: 2,537 population equivalent (BILLINGHAY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBillinghay Water…5 Jan 2025 11:02 GMT, 13 h6 Jan 2025 00:00 GMT, 24 h7 Jan 2025 00:00 GMT, 24 h8 Jan 2025 00:00 GMT, 24 h9 Jan 2025 00:00 GMT, 17.3 h9 Jan 2025 17:32 GMT, 5.7 h9 Jan 2025 23:16 GMT, 2 min9 Jan 2025 23:18 GMT, 2 min9 Jan 2025 23:26 GMT, 2 min9 Jan 2025 23:28 GMT, 32 min10 Jan 2025 00:00 GMT, 6 min10 Jan 2025 03:12 GMT, 20 min10 Jan 2025 03:32 GMT, 2 min10 Jan 2025 08:38 GMT, 2 min10 Jan 2025 08:40 GMT, 3.6 h10 Jan 2025 12:46 GMT, 2 min10 Jan 2025 13:38 GMT, 16 min10 Jan 2025 14:06 GMT, 2 min10 Jan 2025 14:08 GMT, 98 min10 Jan 2025 17:50 GMT, 28 min10 Jan 2025 18:52 GMT, 68 min10 Jan 2025 20:22 GMT, 66 min20 Jan 2025 05:06 GMT, 2 min21 Jan 2025 14:58 GMT, 2 min27 Jan 2025 11:30 GMT, 100 min27 Jan 2025 14:10 GMT, 10 min27 Jan 2025 22:48 GMT, 72 min28 Jan 2025 00:00 GMT, 86 min28 Jan 2025 12:44 GMT, 10 min28 Jan 2025 20:16 GMT, 20 min8 Feb 2025 04:56 GMT, 2 min8 Feb 2025 05:00 GMT, 2 min8 Feb 2025 05:02 GMT, 2 min8 Feb 2025 10:12 GMT, 2 min8 Feb 2025 10:20 GMT, 2 min8 Feb 2025 10:22 GMT, 2 min8 Feb 2025 16:42 GMT, 2 min8 Feb 2025 19:04 GMT, 2 min8 Feb 2025 19:06 GMT, 2 min8 Feb 2025 19:18 GMT, 2 min8 Feb 2025 19:26 GMT, 2 min9 Feb 2025 00:00 GMT, 2 min9 Feb 2025 08:56 GMT, 2 min13 Feb 2025 09:22 GMT, 2 min13 Feb 2025 09:32 GMT, 2 min13 Feb 2025 09:42 GMT, 2 min20 Feb 2025 13:16 GMT, 2 min20 Feb 2025 13:28 GMT, 2 min22 Jun 2025 16:06 GMT, 2 min8 Jul 2025 18:44 GMT, 2 min18 Jul 2025 02:56 GMT, 4 min18 Jul 2025 13:18 GMT, 2 min18 Jul 2025 14:22 GMT, 2 min19 Jul 2025 16:40 GMT, 2.8 h20 Jul 2025 17:54 GMT, 6.1 h21 Jul 2025 00:00 GMT, 4 min22 Jul 2025 12:36 GMT, 4 min22 Jul 2025 16:10 GMT, 2 min22 Jul 2025 17:42 GMT, 2 min23 Jul 2025 05:10 GMT, 2 min23 Jul 2025 14:58 GMT, 2 min23 Jul 2025 16:14 GMT, 2 min31 Jul 2025 13:08 GMT, 2 min31 Jul 2025 14:20 GMT, 2 min31 Jul 2025 14:22 GMT, 2 min31 Jul 2025 15:06 GMT, 2 min31 Jul 2025 15:12 GMT, 2 min31 Jul 2025 15:14 GMT, 2 min31 Jul 2025 15:16 GMT, 2 min31 Jul 2025 19:22 GMT, 2 min1 Aug 2025 00:32 GMT, 2 min1 Aug 2025 03:02 GMT, 2 min1 Aug 2025 03:04 GMT, 2 min1 Aug 2025 03:28 GMT, 6 min1 Aug 2025 03:34 GMT, 2 min1 Aug 2025 04:38 GMT, 2 min1 Aug 2025 04:52 GMT, 2 min1 Aug 2025 05:42 GMT, 6 min1 Aug 2025 23:54 GMT, 2 min2 Aug 2025 01:22 GMT, 4 min2 Aug 2025 01:26 GMT, 2 min2 Aug 2025 01:32 GMT, 2 min3 Aug 2025 10:18 GMT, 2 min17 Sep 2025 08:52 GMT, 4.5 h17 Sep 2025 13:44 GMT, 18 min23 Oct 2025 07:10 GMT, 3.3 h23 Oct 2025 10:32 GMT, 4 min10 Nov 2025 17:10 GMT, 84 min14 Nov 2025 09:38 GMT, 14.4 h15 Nov 2025 00:00 GMT, 22.6 h15 Nov 2025 22:38 GMT, 82 min16 Nov 2025 00:00 GMT, 106 min16 Nov 2025 01:58 GMT, 58 min19 Nov 2025 07:14 GMT, 5.4 h19 Nov 2025 12:48 GMT, 22 min19 Nov 2025 13:16 GMT, 36 min23 Nov 2025 16:32 GMT, 40 min23 Nov 2025 17:46 GMT, 20 min23 Nov 2025 18:48 GMT, 18 min23 Nov 2025 19:46 GMT, 18 min23 Nov 2025 20:32 GMT, 14 min4 Dec 2025 17:58 GMT, 6 h5 Dec 2025 00:00 GMT, 6.5 h5 Dec 2025 06:32 GMT, 5.4 h5 Dec 2025 12:10 GMT, 30 min5 Dec 2025 14:46 GMT, 2.7 h5 Dec 2025 18:54 GMT, 5.1 h6 Dec 2025 00:00 GMT, 2.8 h6 Dec 2025 09:52 GMT, 2.2 h6 Dec 2025 12:32 GMT, 36 min9 Dec 2025 08:26 GMT, 14.5 h16 Dec 2025 06:48 GMT, 17.2 h17 Dec 2025 00:00 GMT, 24 h18 Dec 2025 00:00 GMT, 24 h19 Dec 2025 00:00 GMT, 24 h20 Dec 2025 00:00 GMT, 2.3 h20 Dec 2025 02:40 GMT, 72 min20 Dec 2025 03:56 GMT, 26 min20 Dec 2025 04:42 GMT, 10 min20 Dec 2025 04:58 GMT, 44 min20 Dec 2025 05:52 GMT, 4 min20 Dec 2025 06:14 GMT, 14 min20 Dec 2025 06:38 GMT, 16.9 h20 Dec 2025 23:36 GMT, 16 min21 Dec 2025 00:58 GMT, 18 min21 Dec 2025 06:44 GMT, 22 min21 Dec 2025 07:10 GMT, 2 min21 Dec 2025 07:12 GMT, 26 min21 Dec 2025 08:42 GMT, 15.3 h22 Dec 2025 00:00 GMT, 15 h22 Dec 2025 14:58 GMT, 40 min22 Dec 2025 15:54 GMT, 28 min22 Dec 2025 16:32 GMT, 7.1 h22 Dec 2025 23:42 GMT, 14 min23 Dec 2025 00:02 GMT, 46 min23 Dec 2025 08:58 GMT, 3.8 h23 Dec 2025 12:44 GMT, 10 min23 Dec 2025 13:00 GMT, 14 min23 Dec 2025 13:48 GMT, 54 min23 Dec 2025 18:50 GMT, 74 min23 Dec 2025 20:08 GMT, 16 min23 Dec 2025 20:32 GMT, 68 min23 Dec 2025 21:40 GMT, 4 min24 Dec 2025 14:00 GMT, 2 min24 Dec 2025 16:52 GMT, 18 min24 Dec 2025 18:28 GMT, 8 min24 Dec 2025 18:56 GMT, 54 min24 Dec 2025 19:58 GMT, 24 min24 Dec 2025 22:04 GMT, 2 min24 Dec 2025 22:06 GMT, 4 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

010k20k30kJan 2025: 123 h spilling ≈ 5,325 m³ (range 2,121–13,369 m³)JanFeb 2025: 0.6 h spilling ≈ 26 m³ (range 10–65 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 9.6 h spilling ≈ 417 m³ (range 166–1,048 m³)JulAug 2025: 0.6 h spilling ≈ 26 m³ (range 10–65 m³)AugSep 2025: 4.8 h spilling ≈ 209 m³ (range 83–524 m³)SepOct 2025: 3.4 h spilling ≈ 148 m³ (range 59–371 m³)OctNov 2025: 51 h spilling ≈ 2,204 m³ (range 878–5,533 m³)NovDec 2025: 208 h spilling ≈ 9,046 m³ (range 3,603–22,711 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
19 Dec 2025, 00:00Billinghay Water Recycling Centre1.0 days416 – 2,619 m³
18 Dec 2025, 00:00Billinghay Water Recycling Centre1.0 days416 – 2,619 m³
17 Dec 2025, 00:00Billinghay Water Recycling Centre1.0 days416 – 2,619 m³
8 Jan 2025, 00:00Billinghay Water Recycling Centre1.0 days416 – 2,619 m³
7 Jan 2025, 00:00Billinghay Water Recycling Centre1.0 days416 – 2,619 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate17,401 m³range 6,931 – 43,686 m³
In litres17.4 millionrange 6.9 million – 43.7 million L
Olympic swimming pools7.0at 2,500 m³ each
Organic load, as people's raw sewage26,102person-days of untreated BOD

Assumed spill rate while spilling: 4.8 – 30.3 L/s (central 12.1 L/s), from a dry-weather flow of 4.8 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 277 kg1,566 kg8,737 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 728 kg7,395 kg31,498 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 13 kg110 kg406 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 8.3 kg45 kg236 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 693.1 billion organisms17.4 trillion organisms436.9 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Billinghay Water Recycling Centre

Storm tank at sewage works · discharges to Billinghay Soke Dyke

Spills 2025
48 (400 hours) · down 50% on 2024
Spills 2024
96 (1,021 hours)
Long-term average
72.7 spills a year (monitored since 2023)
Monitor uptime
99% of the year
High-spill reason (company)
Performance - Other maintenance / capital works (e.g. jetting)
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation completed
Improvement
Operational improvement ongoing
WFD catchment
Witham - conf Catchwater Drain to conf Bain (GB205030062425)
Outlet location
TF1626055440 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00091 · ANNNF13035 · company name: BILLINGHAY STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.