Storm overflow register · Anglian Water

Braintree sewage works: storm overflow spills 2025

Braintree sewage treatment works, run by Anglian Water, has 2 monitored storm overflows discharging to The River Brain. In 2025 they recorded 54 spills totalling 92 hours, against 178 spills and 491 hours in 2024. By hours spilling, it ranks 180 of 419 Anglian Water works, where 1 spilled longest.

Works size: 28,087 population equivalent (BRAINTREE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBraintree Water…25 spills, 1.3 h, 1 Jan to 2 Jan133 spills, 36.5 h, 4 Jan to 9 Jan20 Jan 2025 10:04 GMT, 4 min21 spills, 2.1 h, 21 Jan to 22 Jan5 spills, 0.3 h, 23 Jan to 23 Jan80 spills, 7.3 h, 24 Jan to 29 Jan17 spills, 1.3 h, 31 Jan to 31 Jan59 spills, 2.8 h, 1 Feb to 7 Feb29 spills, 2.8 h, 8 Feb to 8 Feb7 spills, 0.3 h, 9 Feb to 9 Feb10 Feb 2025 23:40 GMT, 2 min41 spills, 4.8 h, 13 Feb to 13 Feb3 spills, 0.2 h, 16 Feb to 16 Feb48 spills, 2.3 h, 19 Feb to 21 Feb56 spills, 4.5 h, 22 Feb to 24 Feb28 Feb 2025 14:50 GMT, 2 min30 spills, 1.6 h, 16 Apr to 16 Apr26 spills, 1.2 h, 20 Oct to 23 Oct139 spills, 6.7 h, 24 Oct to 28 Oct19 spills, 0.9 h, 29 Oct to 29 Oct30 Oct 2025 16:22 GMT, 2 minBraintree Water…28 Oct 2025 16:00 GMT, 105 min3 spills, 13.8 h, 14 Nov to 15 Nov

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60kJan 2025: 49 h spilling ≈ 23,485 m³ (range 9,355-58,961 m³)JanFeb 2025: 18 h spilling ≈ 8,566 m³ (range 3,412-21,506 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 1.6 h spilling ≈ 770 m³ (range 307-1,933 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 11 h spilling ≈ 5,101 m³ (range 2,032-12,807 m³)OctNov 2025: 14 h spilling ≈ 6,641 m³ (range 2,645-16,673 m³)NovDec 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 11:58Braintree Water Recycling Centre12.0 h2,307 - 14,539 m³
6 Jan 2025, 04:54Braintree Water Recycling Centre9.6 h1,834 - 11,559 m³
14 Nov 2025, 13:00Braintree Water Recycling Centre7.8 h1,486 - 9,364 m³
15 Nov 2025, 00:00Braintree Water Recycling Centre4.0 h767 - 4,833 m³
14 Nov 2025, 22:00Braintree Water Recycling Centre2.0 h383 - 2,416 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate44,420 m³range 17,693 - 111,518 m³
In litres44.4 millionrange 17.7 million - 111.5 million L
Olympic swimming pools18at 2,500 m³ each
Organic load, as people's raw sewage66,630person-days of untreated BOD

Assumed spill rate while spilling: 53.2 - 335.6 L/s (central 133.7 L/s), from a dry-weather flow of 53.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 708 kg3,998 kg22,304 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,858 kg18,878 kg80,404 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 34 kg280 kg1,037 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 21 kg115 kg602 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.8 trillion organisms44.4 trillion organisms1.1 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Braintree Water Recycling Centre

Storm tank at sewage works · discharges to The River Brain

Spills 2025
51 (77 hours) · down 68% on 2024
Spills 2024
160 (279 hours)
Long-term average
58.8 spills a year (monitored since 2022)
Monitor uptime
96% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, Bathing Water and/or Shellfish Water investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Brain (GB105037041140)
Outlet location
TL7669021760 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00120 · ASENF12212 · company name: BRAINTREE STW

Braintree Water Recycling Centre

Inlet overflow at sewage works · discharges to The River Brain

Spills 2025
3 (16 hours) · down 83% on 2024
Spills 2024
18 (212 hours)
Long-term average
13.3 spills a year (monitored since 2023)
Monitor uptime
38% of the year · Telemetry or data archiving failure / issue
Investigation
Env Act (SODRP) investigation ongoing, Bathing Water and/or Shellfish Water investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Brain (GB105037041140)
Outlet location
TL7669021760 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00121 · ASENF12212 · company name: BRAINTREE STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.