Storm overflow register · Anglian Water

Buckden sewage works: storm overflow spills 2025

Buckden sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Tributary of Diddington Brook. In 2025 it recorded 66 spills totalling 731 hours, against 162 spills and 3,033 hours in 2024. By hours spilling, it ranks 20 of 419 Anglian Water works, where 1 spilled longest.

Works size: 5,113 population equivalent (BUCKDEN STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBuckden Water…1215 spills, 651.6 h, 1 Jan to 20 Feb3 spills, 0.4 h, 26 Feb to 26 Feb25 Jun 2025 11:34 GMT, 18 min6 spills, 3.2 h, 19 Jul to 19 Jul4 spills, 1.1 h, 20 Jul to 20 Jul4 Aug 2025 17:50 GMT, 64 min19 spills, 47.1 h, 13 Nov to 16 Nov59 spills, 12.2 h, 19 Nov to 19 Nov3 spills, 5.8 h, 22 Nov to 23 Nov18 spills, 2.3 h, 9 Dec to 9 Dec19 spills, 5.8 h, 18 Dec to 18 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

025k50k75k100kJan 2025: 428 h spilling ≈ 37,470 m³ (range 14,925-94,070 m³)JanFeb 2025: 224 h spilling ≈ 19,651 m³ (range 7,827-49,333 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.3 h spilling ≈ 26 m³ (range 10-66 m³)JunJul 2025: 4.3 h spilling ≈ 377 m³ (range 150-946 m³)JulAug 2025: 1.1 h spilling ≈ 96 m³ (range 38-242 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 65 h spilling ≈ 5,703 m³ (range 2,272-14,318 m³)NovDec 2025: 8.1 h spilling ≈ 710 m³ (range 283-1,782 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
7 Jan 2025, 00:00Buckden Water Recycling Centre1.0 days838 - 5,279 m³
6 Jan 2025, 00:00Buckden Water Recycling Centre1.0 days838 - 5,279 m³
8 Jan 2025, 00:00Buckden Water Recycling Centre23.9 h834 - 5,257 m³
5 Jan 2025, 06:22Buckden Water Recycling Centre17.6 h615 - 3,878 m³
14 Nov 2025, 06:32Buckden Water Recycling Centre17.5 h610 - 3,842 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate64,015 m³range 25,499 - 160,713 m³
In litres64.0 millionrange 25.5 million - 160.7 million L
Olympic swimming pools26at 2,500 m³ each
Organic load, as people's raw sewage96,023person-days of untreated BOD

Assumed spill rate while spilling: 9.7 - 61.1 L/s (central 24.3 L/s), from a dry-weather flow of 9.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,020 kg5,761 kg32,143 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,677 kg27,207 kg115,874 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 48 kg403 kg1,495 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 31 kg166 kg868 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.5 trillion organisms64.0 trillion organisms1.6 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Buckden Water Recycling Centre

Storm tank at sewage works · discharges to Tributary of Diddington Brook

Spills 2025
66 (731 hours) · down 59% on 2024
Spills 2024
162 (3,033 hours)
Long-term average
116.0 spills a year (monitored since 2023)
Monitor uptime
100% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation completed
Improvement
Operational improvement ongoing
WFD catchment
Diddington Brook (GB105033043310)
Outlet location
TL1997067050 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00164 · AWCNF11413 · company name: BUCKDEN STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.