Storm overflow register · Anglian Water

Deeping sewage works: storm overflow spills 2025

Deeping sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to River Welland. In 2025 it recorded 53 spills totalling 789 hours, against 131 spills and 1,473 hours in 2024. By hours spilling, it ranks 15 of 419 Anglian Water works, where 1 spilled longest.

Works size: 17,866 population equivalent (DEEPINGS STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecDeeping Water…49 spills, 76 h, 1 Jan to 6 Jan10 spills, 185.5 h, 9 Jan to 16 Jan24 spills, 59.5 h, 14 Nov to 17 Nov15 spills, 4.8 h, 19 Nov to 19 Nov19 spills, 50 h, 22 Nov to 25 Nov64 spills, 228.3 h, 1 Dec to 15 Dec8 spills, 17.8 h, 15 Dec to 17 Dec74 spills, 162.8 h, 17 Dec to 27 Dec3 spills, 4 h, 28 Dec to 28 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0100k200k300k400kJan 2025: 262 h spilling ≈ 80,051 m³ (range 31,886-200,972 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)OctNov 2025: 114 h spilling ≈ 34,959 m³ (range 13,925-87,767 m³)NovDec 2025: 413 h spilling ≈ 126,368 m³ (range 50,335-317,252 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
19 Dec 2025, 00:00Deeping Water Recycling Centre1.0 days2,926 - 18,445 m³
6 Dec 2025, 00:00Deeping Water Recycling Centre1.0 days2,926 - 18,445 m³
15 Nov 2025, 00:00Deeping Water Recycling Centre1.0 days2,926 - 18,445 m³
15 Jan 2025, 00:00Deeping Water Recycling Centre1.0 days2,926 - 18,445 m³
14 Jan 2025, 00:00Deeping Water Recycling Centre1.0 days2,926 - 18,445 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate241,379 m³range 96,146 - 605,990 m³
In litres241.4 millionrange 96.1 million - 606.0 million L
Olympic swimming pools97at 2,500 m³ each
Organic load, as people's raw sewage362,068person-days of untreated BOD

Assumed spill rate while spilling: 33.9 - 213.5 L/s (central 85.0 L/s), from a dry-weather flow of 33.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 3,846 kg21,724 kg121,198 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 10,095 kg102,586 kg436,919 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 183 kg1,521 kg5,636 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 115 kg628 kg3,272 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 9.6 trillion organisms241.4 trillion organisms6.1 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Deeping Water Recycling Centre

Storm tank at sewage works · discharges to River Welland

Spills 2025
53 (789 hours) · down 60% on 2024
Spills 2024
131 (1,473 hours)
Long-term average
67.6 spills a year (monitored since 2021)
Monitor uptime
99% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Welland - conf Greatford Cut to tidal (GB205031050685)
Outlet location
TF1711008150 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00324 · ANNNF13012 · company name: Deeping Water Recycling Centre

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.