Storm overflow register · Anglian Water

Feltwell sewage works: storm overflow spills 2025

Feltwell sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Cut-Off Channel. In 2025 it recorded 12 spills totalling 47 hours, against 192 spills and 4,145 hours in 2024. By hours spilling, it ranks 234 of 419 Anglian Water works, where 1 spilled longest.

Works size: 2,082 population equivalent (FELTWELL STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFeltwell Water…1 Jan 2025 11:00 GMT, 4.3 h5 Jan 2025 12:45 GMT, 8.8 h6 Jan 2025 08:30 GMT, 60 min6 Jan 2025 10:30 GMT, 75 min6 Jan 2025 11:45 GMT, 15 min6 Jan 2025 12:00 GMT, 15 min10 Jan 2025 07:45 GMT, 60 min11 Jan 2025 15:45 GMT, 60 min12 Jan 2025 10:15 GMT, 4.8 h13 Jan 2025 11:00 GMT, 60 min13 Jan 2025 16:30 GMT, 5.3 h16 Jan 2025 09:00 GMT, 2 h17 Jan 2025 16:30 GMT, 4 h18 Jan 2025 10:45 GMT, 6 h20 Jan 2025 07:30 GMT, 6.5 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

02,0004,0006,000Jan 2025: 47 h spilling ≈ 1,684 m³ (range 671–4,227 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)NovDec 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 12:45Feltwell Water Recycling Centre8.8 h124 – 784 m³
20 Jan 2025, 07:30Feltwell Water Recycling Centre6.5 h92 – 582 m³
18 Jan 2025, 10:45Feltwell Water Recycling Centre6.0 h85 – 537 m³
13 Jan 2025, 16:30Feltwell Water Recycling Centre5.3 h75 – 470 m³
12 Jan 2025, 10:15Feltwell Water Recycling Centre4.8 h67 – 425 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate1,684 m³range 671 – 4,227 m³
In litres1.7 millionrange 670,695 – 4.2 million L
Olympic swimming pools0.7at 2,500 m³ each
Organic load, as people's raw sewage2,526person-days of untreated BOD

Assumed spill rate while spilling: 3.9 – 24.9 L/s (central 9.9 L/s), from a dry-weather flow of 3.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 27 kg152 kg845 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 70 kg716 kg3,048 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1.3 kg11 kg39 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 0.8 kg4.4 kg23 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 67.1 billion organisms1.7 trillion organisms42.3 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Feltwell Water Recycling Centre

Storm tank at sewage works · discharges to Cut-Off Channel

Spills 2025
12 (47 hours) · down 94% on 2024
Spills 2024
192 (4,145 hours)
Long-term average
69.2 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Cut-off Channel (GB205033000040)
Outlet location
TL7003090760 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00429 · AW1NF213 · company name: FELTWELL STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.