Storm overflow register · Anglian Water

Horncastle sewage works: storm overflow spills 2025

Horncastle sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Old River Bain. In 2025 it recorded 34 spills totalling 493 hours, against 69 spills and 1,331 hours in 2024. By hours spilling, it ranks 43 of 419 Anglian Water works, where 1 spilled longest.

Works size: 8,954 population equivalent (HORNCASTLE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHorncastle Water…5 Jan 2025 17:10 GMT, 16 min5 Jan 2025 22:48 GMT, 36 min6 Jan 2025 00:24 GMT, 23.6 h7 Jan 2025 00:00 GMT, 24 h8 Jan 2025 00:00 GMT, 24 h9 Jan 2025 00:00 GMT, 24 h10 Jan 2025 00:00 GMT, 24 h11 Jan 2025 00:00 GMT, 24 h12 Jan 2025 00:00 GMT, 10 min12 Jan 2025 21:20 GMT, 2.7 h13 Jan 2025 00:00 GMT, 24 h14 Jan 2025 00:00 GMT, 2.9 h29 Jan 2025 12:02 GMT, 12 h30 Jan 2025 00:00 GMT, 4.8 h24 Feb 2025 12:38 GMT, 24 min6 Jul 2025 16:10 GMT, 8 min19 Jul 2025 14:50 GMT, 6 min19 Jul 2025 14:56 GMT, 2 min19 Jul 2025 16:08 GMT, 44 min20 Jul 2025 11:54 GMT, 24 min20 Jul 2025 14:22 GMT, 70 min20 Jul 2025 15:34 GMT, 2 min20 Jul 2025 15:36 GMT, 2 min20 Jul 2025 16:08 GMT, 22 min20 Jul 2025 16:30 GMT, 2 min20 Jul 2025 16:32 GMT, 4 min20 Jul 2025 16:36 GMT, 2 min20 Jul 2025 20:02 GMT, 2 min3 Sep 2025 12:12 GMT, 46 min15 Nov 2025 06:52 GMT, 17.1 h16 Nov 2025 00:00 GMT, 2.6 h7 Dec 2025 16:46 GMT, 74 min8 Dec 2025 11:52 GMT, 4.3 h8 Dec 2025 19:12 GMT, 3.9 h9 Dec 2025 03:58 GMT, 20 h10 Dec 2025 00:00 GMT, 24 h11 Dec 2025 00:00 GMT, 24 h12 Dec 2025 14:46 GMT, 6 h13 Dec 2025 00:00 GMT, 78 min15 Dec 2025 22:28 GMT, 2 min15 Dec 2025 22:36 GMT, 2 min15 Dec 2025 22:40 GMT, 76 min16 Dec 2025 01:14 GMT, 16 min16 Dec 2025 04:10 GMT, 19.8 h17 Dec 2025 00:00 GMT, 24 h18 Dec 2025 00:00 GMT, 24 h19 Dec 2025 00:00 GMT, 24 h20 Dec 2025 00:00 GMT, 24 h21 Dec 2025 00:00 GMT, 24 h22 Dec 2025 00:00 GMT, 24 h23 Dec 2025 00:00 GMT, 24 h27 Dec 2025 10:34 GMT, 3.4 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150kJan 2025: 191 h spilling ≈ 29,304 m³ (range 11,672–73,568 m³)JanFeb 2025: 0.4 h spilling ≈ 61 m³ (range 24–154 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 3.2 h spilling ≈ 491 m³ (range 196–1,233 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.8 h spilling ≈ 123 m³ (range 49–308 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 20 h spilling ≈ 3,022 m³ (range 1,204–7,588 m³)NovDec 2025: 278 h spilling ≈ 42,590 m³ (range 16,964–106,924 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
23 Dec 2025, 00:00Horncastle Water Recycling Centre1.0 days1,467 – 9,244 m³
22 Dec 2025, 00:00Horncastle Water Recycling Centre1.0 days1,467 – 9,244 m³
21 Dec 2025, 00:00Horncastle Water Recycling Centre1.0 days1,467 – 9,244 m³
20 Dec 2025, 00:00Horncastle Water Recycling Centre1.0 days1,467 – 9,244 m³
19 Dec 2025, 00:00Horncastle Water Recycling Centre1.0 days1,467 – 9,244 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate75,576 m³range 30,103 – 189,735 m³
In litres75.6 millionrange 30.1 million – 189.7 million L
Olympic swimming pools30at 2,500 m³ each
Organic load, as people's raw sewage113,363person-days of untreated BOD

Assumed spill rate while spilling: 17.0 – 107.0 L/s (central 42.6 L/s), from a dry-weather flow of 17.0 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,204 kg6,802 kg37,947 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 3,161 kg32,120 kg136,799 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 57 kg476 kg1,765 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 36 kg196 kg1,025 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 3.0 trillion organisms75.6 trillion organisms1.9 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Horncastle Water Recycling Centre

Storm tank at sewage works · discharges to Old River Bain

Spills 2025
34 (493 hours) · down 51% on 2024
Spills 2024
69 (1,331 hours)
Long-term average
52.0 spills a year (monitored since 2023)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Bain - Lower (GB105030062450)
Outlet location
TF2595067440 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS00617 · ANNNF10519 · company name: HORNCASTLE STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.