Storm overflow register · Anglian Water

Sawtry sewage works: storm overflow spills 2025

Sawtry sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Trib of Middle Level Catch Drn. In 2025 it recorded 14 spills totalling 124 hours, against 67 spills and 1,201 hours in 2024. By hours spilling, it ranks 155 of 419 Anglian Water works, where 1 spilled longest.

Works size: 6,257 population equivalent (SAWTRY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSawtry Water…6 Jan 2025 05:32 GMT, 2.1 h6 Jan 2025 08:14 GMT, 15.8 h7 Jan 2025 00:00 GMT, 5.7 h7 Jan 2025 05:42 GMT, 2 min7 Jan 2025 05:44 GMT, 2 min7 Jan 2025 07:24 GMT, 62 min7 Jan 2025 09:30 GMT, 2 min29 Jan 2025 01:10 GMT, 6 min29 Jan 2025 01:16 GMT, 2 min30 Jun 2025 10:02 GMT, 6 min14 Nov 2025 10:46 GMT, 13.2 h15 Nov 2025 00:00 GMT, 24 h16 Nov 2025 00:00 GMT, 64 min16 Nov 2025 01:08 GMT, 26 min16 Nov 2025 01:46 GMT, 24 min22 Nov 2025 20:34 GMT, 3.4 h23 Nov 2025 00:00 GMT, 54 min23 Nov 2025 00:54 GMT, 60 min23 Nov 2025 07:16 GMT, 7.9 h23 Nov 2025 15:08 GMT, 2 min23 Nov 2025 15:10 GMT, 26 min23 Nov 2025 15:36 GMT, 2 min23 Nov 2025 15:40 GMT, 26 min23 Nov 2025 16:08 GMT, 28 min23 Nov 2025 16:40 GMT, 26 min23 Nov 2025 17:10 GMT, 24 min23 Nov 2025 17:34 GMT, 2 min23 Nov 2025 17:40 GMT, 26 min23 Nov 2025 18:12 GMT, 24 min23 Nov 2025 18:42 GMT, 26 min23 Nov 2025 19:12 GMT, 12 min23 Nov 2025 19:48 GMT, 24 min23 Nov 2025 20:22 GMT, 24 min29 Nov 2025 18:02 GMT, 6 h30 Nov 2025 00:00 GMT, 28 min30 Nov 2025 00:30 GMT, 24 min6 Dec 2025 01:32 GMT, 4 h6 Dec 2025 05:34 GMT, 2 min6 Dec 2025 06:58 GMT, 7 h6 Dec 2025 13:56 GMT, 2 min6 Dec 2025 13:58 GMT, 40 min6 Dec 2025 14:42 GMT, 2 min6 Dec 2025 14:44 GMT, 2 min6 Dec 2025 15:18 GMT, 14 min6 Dec 2025 16:38 GMT, 12 min6 Dec 2025 17:58 GMT, 12 min18 Dec 2025 18:40 GMT, 5.3 h19 Dec 2025 00:00 GMT, 8.4 h19 Dec 2025 08:38 GMT, 78 min19 Dec 2025 10:02 GMT, 4.9 h19 Dec 2025 15:54 GMT, 54 min19 Dec 2025 17:22 GMT, 26 min19 Dec 2025 18:16 GMT, 10 min19 Dec 2025 18:38 GMT, 2 min19 Dec 2025 18:56 GMT, 10 min19 Dec 2025 19:32 GMT, 22 min19 Dec 2025 20:04 GMT, 2 min19 Dec 2025 20:08 GMT, 26 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

05,00010k15k20kJan 2025: 25 h spilling ≈ 2,659 m³ (range 1,059–6,675 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.1 h spilling ≈ 11 m³ (range 4.3–27 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 64 h spilling ≈ 6,829 m³ (range 2,720–17,145 m³)NovDec 2025: 35 h spilling ≈ 3,742 m³ (range 1,490–9,394 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
15 Nov 2025, 00:00Sawtry Water Recycling Centre1.0 days1,025 – 6,460 m³
6 Jan 2025, 08:14Sawtry Water Recycling Centre15.8 h673 – 4,244 m³
14 Nov 2025, 10:46Sawtry Water Recycling Centre13.2 h565 – 3,562 m³
19 Dec 2025, 00:00Sawtry Water Recycling Centre8.4 h360 – 2,270 m³
23 Nov 2025, 07:16Sawtry Water Recycling Centre7.9 h336 – 2,117 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate13,240 m³range 5,274 – 33,241 m³
In litres13.2 millionrange 5.3 million – 33.2 million L
Olympic swimming pools5.3at 2,500 m³ each
Organic load, as people's raw sewage19,861person-days of untreated BOD

Assumed spill rate while spilling: 11.9 – 74.8 L/s (central 29.8 L/s), from a dry-weather flow of 11.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 211 kg1,192 kg6,648 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 554 kg5,627 kg23,967 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 10 kg83 kg309 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 6.3 kg34 kg179 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 527.4 billion organisms13.2 trillion organisms332.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Sawtry Water Recycling Centre

Storm tank at sewage works · discharges to Trib of Middle Level Catch Drn

Spills 2025
14 (124 hours) · down 79% on 2024
Spills 2024
67 (1,201 hours)
Long-term average
47.3 spills a year (monitored since 2022)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Middle Level (GB205033000050)
Outlet location
TL1799082650 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01099 · AWCNF1187 · company name: SAWTRY STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.