Storm overflow register · Anglian Water

Sleaford sewage works: storm overflow spills 2025

Sleaford sewage treatment works, run by Anglian Water, has 2 monitored storm overflows discharging to Old River Slea. In 2025 they recorded 48 spills totalling 244 hours, against 135 spills and 1,686 hours in 2024. By hours spilling, it ranks 91 of 419 Anglian Water works, where 1 spilled longest.

Works size: 17,945 population equivalent (SLEAFORD STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSleaford Water…56 spills, 69.4 h, 5 Jan to 8 Jan3 spills, 0.4 h, 10 Jan to 10 Jan3 spills, 0.1 h, 12 Jan to 12 Jan2 spills, 1.4 h, 15 Jan to 16 Jan8 spills, 1.3 h, 16 Jan to 16 Jan7 spills, 0.7 h, 17 Jan to 17 Jan9 spills, 0.6 h, 18 Jan to 18 Jan10 spills, 1 h, 19 Jan to 20 Jan39 spills, 5.9 h, 26 Jan to 28 Jan4 spills, 0.3 h, 23 Oct to 23 Oct79 spills, 5.8 h, 10 Nov to 12 Nov428 spills, 28.7 h, 14 Nov to 18 Nov17 spills, 1.2 h, 19 Nov to 19 Nov43 spills, 11.7 h, 22 Nov to 24 Nov96 spills, 10.2 h, 4 Dec to 6 Dec4 spills, 0.2 h, 9 Dec to 9 Dec132 spills, 74.1 h, 16 Dec to 21 Dec17 spills, 5.9 h, 21 Dec to 23 DecSleaford Water…4 spills, 14 h, 6 Jan to 6 Jan19 Jul 2025 14:45 GMT, 30 min16 spills, 4.3 h, 14 Nov to 15 Nov3 spills, 0.8 h, 4 Dec to 4 Dec5 spills, 4.3 h, 16 Dec to 16 Dec5 spills, 1.3 h, 18 Dec to 18 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

020k40k60k80kJan 2025: 95 h spilling ≈ 29,118 m³ (range 11,598-73,102 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.5 h spilling ≈ 154 m³ (range 61-386 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)SepOct 2025: 0.3 h spilling ≈ 92 m³ (range 37-232 m³)OctNov 2025: 52 h spilling ≈ 15,835 m³ (range 6,307-39,755 m³)NovDec 2025: 97 h spilling ≈ 29,702 m³ (range 11,831-74,569 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
6 Jan 2025, 00:46Sleaford Water Recycling Centre23.2 h2,845 - 17,935 m³
16 Dec 2025, 07:22Sleaford Water Recycling Centre16.6 h2,037 - 12,840 m³
6 Jan 2025, 01:00Sleaford Water Recycling Centre13.3 h1,623 - 10,228 m³
7 Jan 2025, 07:00Sleaford Water Recycling Centre11.3 h1,384 - 8,723 m³
18 Dec 2025, 13:50Sleaford Water Recycling Centre10.2 h1,245 - 7,848 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate74,871 m³range 29,823 - 187,966 m³
In litres74.9 millionrange 29.8 million - 188.0 million L
Olympic swimming pools30at 2,500 m³ each
Organic load, as people's raw sewage112,306person-days of untreated BOD

Assumed spill rate while spilling: 34.0 - 214.4 L/s (central 85.4 L/s), from a dry-weather flow of 34.0 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,193 kg6,738 kg37,593 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 3,131 kg31,820 kg135,523 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 57 kg472 kg1,748 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 36 kg195 kg1,015 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 3.0 trillion organisms74.9 trillion organisms1.9 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Sleaford Water Recycling Centre

Storm tank at sewage works · discharges to Old River Slea

Spills 2025
40 (219 hours) · down 57% on 2024
Spills 2024
94 (961 hours)
Long-term average
63.8 spills a year (monitored since 2022)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Slea (GB105030056670)
Outlet location
TF0862047210 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01145 · ANNNF13036 · company name: SLEAFORD WRC

Sleaford Water Recycling Centre

Inlet overflow at sewage works · discharges to Old River Slea

Spills 2025
8 (25 hours) · down 80% on 2024
Spills 2024
41 (725 hours)
Long-term average
24.5 spills a year (monitored since 2024)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Slea (GB105030056670)
Outlet location
TF0862047210 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01146 · ANNNF13036 · company name: SLEAFORD WRC

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.