Storm overflow register · Anglian Water

Southend sewage works: storm overflow spills 2025

Southend sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Thames Estuary. In 2025 it recorded 94 spills totalling 237 hours, against 43 spills and 196 hours in 2024. By hours spilling, it ranks 93 of 419 Anglian Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSouthend Sewage Works3 spills, 6 h, 1 Jan to 1 Jan66 spills, 37.4 h, 4 Jan to 6 Jan2 spills, 0.1 h, 7 Jan to 7 Jan7 spills, 3.2 h, 8 Jan to 8 Jan2 spills, 0.2 h, 23 Jan to 23 Jan24 spills, 4.4 h, 26 Jan to 27 Jan5 spills, 0.4 h, 28 Jan to 28 Jan5 spills, 2.7 h, 31 Jan to 31 Jan1 Feb 2025 11:44 GMT, 4 min26 spills, 5.2 h, 7 Feb to 8 Feb5 spills, 0.4 h, 9 Feb to 9 Feb11 spills, 4.5 h, 10 Feb to 10 Feb14 spills, 4.5 h, 22 Feb to 22 Feb11 spills, 4 h, 24 Feb to 24 Feb5 spills, 3.5 h, 26 Feb to 26 Feb3 spills, 10 h, 15 Apr to 15 Apr6 spills, 0.5 h, 21 Apr to 21 Apr3 spills, 7 h, 23 Apr to 23 Apr2 May 2025 08:32 GMT, 2 min2 spills, 0.1 h, 3 May to 3 May4 May 2025 09:26 GMT, 4 min6 May 2025 08:32 GMT, 2 min2 spills, 0.1 h, 7 May to 7 May8 May 2025 08:30 GMT, 4 min2 spills, 0.1 h, 9 May to 9 May2 spills, 0.1 h, 10 May to 10 May12 May 2025 08:36 GMT, 4 min2 spills, 0.1 h, 14 May to 14 May2 spills, 0.1 h, 22 May to 22 May4 spills, 4.6 h, 24 May to 24 May25 May 2025 11:58 GMT, 2 min4 spills, 2 h, 27 May to 27 May5 Jun 2025 22:20 GMT, 2 min12 spills, 5.5 h, 7 Jun to 8 Jun4 spills, 2.3 h, 13 Jun to 14 Jun44 spills, 6.2 h, 7 Jul to 9 Jul7 spills, 0.4 h, 15 Jul to 16 Jul90 spills, 34.1 h, 18 Jul to 23 Jul4 spills, 2.9 h, 24 Jul to 24 Jul3 spills, 0.7 h, 1 Aug to 1 Aug2 spills, 0.1 h, 11 Aug to 11 Aug2 spills, 0.2 h, 28 Aug to 28 Aug5 spills, 6.2 h, 29 Aug to 30 Aug31 Oct 2025 09:26 GMT, 2 min20 spills, 8.6 h, 1 Nov to 4 Nov2 spills, 0.1 h, 5 Nov to 5 Nov4 spills, 0.2 h, 6 Nov to 6 Nov3 spills, 0.2 h, 7 Nov to 7 Nov6 spills, 0.4 h, 8 Nov to 8 Nov7 spills, 0.6 h, 9 Nov to 9 Nov20 spills, 5.3 h, 10 Nov to 11 Nov5 spills, 0.3 h, 12 Nov to 12 Nov43 spills, 20.2 h, 13 Nov to 16 Nov11 spills, 4.3 h, 17 Nov to 19 Nov2 spills, 0.1 h, 20 Nov to 20 Nov3 spills, 0.2 h, 21 Nov to 21 Nov6 spills, 9.4 h, 22 Nov to 23 Nov26 Nov 2025 10:22 GMT, 8 min5 spills, 2.3 h, 2 Dec to 3 Dec2 spills, 1.8 h, 4 Dec to 4 Dec2 spills, 1.8 h, 7 Dec to 7 Dec4 spills, 2.9 h, 9 Dec to 9 Dec13 spills, 12.8 h, 18 Dec to 18 Dec7 spills, 4.1 h, 21 Dec to 21 Dec25 Dec 2025 11:52 GMT, 8 min6 spills, 0.4 h, 26 Dec to 26 Dec30 Dec 2025 11:40 GMT, 4 min31 Dec 2025 11:22 GMT, 6 min

Hours spilling by month, 2025

0204060Jan 2025: 54 hours spillingJanFeb 2025: 22 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 18 hours spillingAprMay 2025: 7.6 hours spillingMayJun 2025: 7.8 hours spillingJunJul 2025: 44 hours spillingJulAug 2025: 7.2 hours spillingAugSep 2025: 0.0 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 50 hours spillingNovDec 2025: 26 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
5 Jan 2025, 00:30Southend Sewage Works23.5 h
21 Jul 2025, 04:46Southend Sewage Works19.2 h
18 Dec 2025, 12:50Southend Sewage Works10.0 h
15 Apr 2025, 03:04Southend Sewage Works9.7 h
14 Nov 2025, 07:48Southend Sewage Works7.9 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate4,056 m³range 1,615 - 10,182 m³
In litres4.1 millionrange 1.6 million - 10.2 million L
Olympic swimming pools1.6at 2,500 m³ each
Organic load, as people's raw sewage6,084person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 65 kg365 kg2,036 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 170 kg1,724 kg7,341 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 3.1 kg26 kg95 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1.9 kg11 kg55 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 161.5 billion organisms4.1 trillion organisms101.8 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Southend Sewage Works

Inlet overflow at sewage works · discharges to Thames Estuary

Spills 2025
94 (237 hours) · up 119% on 2024
Spills 2024
43 (196 hours)
Long-term average
78.0 spills a year (monitored since 2021)
Monitor uptime
28% of the year · Telemetry or data archiving failure / issue
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, Bathing Water and/or Shellfish Water investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
THAMES LOWER (GB530603911401)
Outlet location
TQ9070081920 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01194 · CASM.0072 · company name: SOUTHEND STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.