Storm overflow register · Anglian Water

Thealby sewage works: storm overflow spills 2025

Thealby sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to Unknown trib.. In 2025 it recorded 80 spills totalling 770 hours, against 90 spills and 766 hours in 2024. By hours spilling, it ranks 17 of 419 Anglian Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecThealby STW2 spills, 48 h, 1 Jan to 3 Jan3 spills, 72 h, 5 Jan to 8 Jan2 spills, 0.8 h, 9 Jan to 10 Jan9 spills, 15.5 h, 26 Jan to 28 Jan9 Feb 2025 00:30 GMT, 75 min2 spills, 1.5 h, 23 Feb to 24 Feb2 spills, 1.3 h, 26 Feb to 26 Feb14 Mar 2025 17:15 GMT, 15 min24 May 2025 03:15 GMT, 75 min1 Jun 2025 16:15 GMT, 15 min4 spills, 2.5 h, 5 Jun to 6 Jun10 Jun 2025 00:45 GMT, 45 min22 Jun 2025 21:30 GMT, 60 min4 Aug 2025 09:45 GMT, 15 min11 Aug 2025 13:15 GMT, 15 min28 Aug 2025 14:15 GMT, 45 min29 Aug 2025 14:15 GMT, 30 min30 Aug 2025 22:00 GMT, 30 min2 spills, 2.8 h, 4 Sep to 4 Sep10 Sep 2025 20:15 GMT, 60 min3 spills, 1 h, 11 Sep to 11 Sep14 Sep 2025 20:45 GMT, 30 min17 Sep 2025 05:00 GMT, 4 h2 spills, 12 h, 20 Sep to 21 Sep28 Sep 2025 04:30 GMT, 45 min3 spills, 2.8 h, 2 Oct to 3 Oct5 spills, 4 h, 19 Oct to 20 Oct2 spills, 2 h, 23 Oct to 23 Oct25 Oct 2025 00:15 GMT, 30 min31 Oct 2025 15:00 GMT, 30 min4 Nov 2025 17:15 GMT, 5.8 h5 Nov 2025 18:00 GMT, 90 min11 spills, 36.3 h, 10 Nov to 13 Nov35 spills, 118.3 h, 14 Nov to 20 Nov8 spills, 8 h, 21 Nov to 23 Nov4 spills, 4 h, 26 Nov to 27 Nov6 spills, 127.8 h, 29 Nov to 5 Dec5 spills, 120 h, 6 Dec to 11 Dec13 Dec 2025 00:00 GMT, 24 h5 spills, 120 h, 15 Dec to 20 Dec22 Dec 2025 00:00 GMT, 24 h

Hours spilling by month, 2025

0100200300400Jan 2025: 136 hours spillingJanFeb 2025: 4.0 hours spillingFebMar 2025: 0.2 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 1.2 hours spillingMayJun 2025: 4.5 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 2.2 hours spillingAugSep 2025: 22 hours spillingSepOct 2025: 9.8 hours spillingOctNov 2025: 217 hours spillingNovDec 2025: 372 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
22 Dec 2025, 00:00Thealby STW1.0 days
19 Dec 2025, 00:00Thealby STW1.0 days
18 Dec 2025, 00:00Thealby STW1.0 days
17 Dec 2025, 00:00Thealby STW1.0 days
16 Dec 2025, 00:00Thealby STW1.0 days

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate13,190 m³range 5,254 - 33,114 m³
In litres13.2 millionrange 5.3 million - 33.1 million L
Olympic swimming pools5.3at 2,500 m³ each
Organic load, as people's raw sewage19,785person-days of untreated BOD

Assumed spill rate while spilling: 1.9 - 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 210 kg1,187 kg6,623 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 552 kg5,606 kg23,875 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 10.0 kg83 kg308 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 6.3 kg34 kg179 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 525.4 billion organisms13.2 trillion organisms331.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Thealby STW

Inlet overflow at sewage works · discharges to Unknown trib.

Spills 2025
80 (770 hours) · down 11% on 2024
Spills 2024
90 (766 hours)
Long-term average
85.0 spills a year (monitored since 2024)
Monitor uptime
99% of the year
High-spill reason (company)
Performance - Other maintenance / capital works (e.g. jetting)
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Winterton Beck from Source to the Humber (GB104029067660)
Outlet location
SE8950018200 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01362 · AW3NF383

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.