Storm overflow register · Anglian Water

Wickham Market sewage works: storm overflow spills 2025

Wickham Market sewage treatment works, run by Anglian Water, has 1 monitored storm overflow discharging to River Deben. In 2025 it recorded 13 spills totalling 129 hours, against 34 spills and 533 hours in 2024. By hours spilling, it ranks 152 of 419 Anglian Water works, where 1 spilled longest.

Works size: 2,715 population equivalent (WICKHAM MARKET STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWickham Market WRC6 Jan 2025 06:45 GMT, 17.3 h7 Jan 2025 00:00 GMT, 24 h8 Jan 2025 00:00 GMT, 45 min28 Jan 2025 05:45 GMT, 15 min28 Jan 2025 06:00 GMT, 9 h29 Jan 2025 18:00 GMT, 15 min29 Jan 2025 18:15 GMT, 5.8 h14 Jun 2025 01:15 GMT, 3 h17 Jul 2025 12:00 GMT, 45 min21 Jul 2025 09:15 GMT, 3.5 h14 Nov 2025 13:00 GMT, 10.8 h14 Nov 2025 23:45 GMT, 15 min15 Nov 2025 00:00 GMT, 45 min15 Nov 2025 08:00 GMT, 16 h16 Nov 2025 00:00 GMT, 15.5 h24 Nov 2025 03:15 GMT, 20.8 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

02,0004,0006,0008,000Jan 2025: 57 h spilling ≈ 2,661 m³ (range 1,060–6,680 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 3.0 h spilling ≈ 140 m³ (range 56–350 m³)JunJul 2025: 4.2 h spilling ≈ 195 m³ (range 78–491 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 64 h spilling ≈ 2,977 m³ (range 1,186–7,475 m³)NovDec 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
7 Jan 2025, 00:00Wickham Market WRC1.0 days445 – 2,803 m³
24 Nov 2025, 03:15Wickham Market WRC20.8 h384 – 2,423 m³
6 Jan 2025, 06:45Wickham Market WRC17.3 h320 – 2,015 m³
15 Nov 2025, 08:00Wickham Market WRC16.0 h296 – 1,869 m³
16 Nov 2025, 00:00Wickham Market WRC15.5 h287 – 1,810 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate5,978 m³range 2,381 – 15,008 m³
In litres6.0 millionrange 2.4 million – 15.0 million L
Olympic swimming pools2.4at 2,500 m³ each
Organic load, as people's raw sewage8,967person-days of untreated BOD

Assumed spill rate while spilling: 5.1 – 32.4 L/s (central 12.9 L/s), from a dry-weather flow of 5.1 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 95 kg538 kg3,002 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 250 kg2,541 kg10,820 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 4.5 kg38 kg140 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 2.9 kg16 kg81 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 238.1 billion organisms6.0 trillion organisms150.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Wickham Market WRC

Storm tank at sewage works · discharges to River Deben

Spills 2025
13 (129 hours) · down 62% on 2024
Spills 2024
34 (533 hours)
Long-term average
32.5 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, Bathing Water and/or Shellfish Water investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Deben (Brandeston Bridge - Melton) (GB105035046310)
Outlet location
TM3094055960 (OS grid reference) · View on Apple Maps
EA ID / permit
AWS01498 · ASENF10537 · company name: WICKHAM MARKET STW

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Anglian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.