Storm overflow register · Northumbrian Water

Birtley sewage works: storm overflow spills 2025

Birtley sewage treatment works, run by Northumbrian Water, has 2 monitored storm overflows discharging to Team. In 2025 they recorded 44 spills totalling 247 hours, against 98 spills and 722 hours in 2024. By hours spilling, it ranks 82 of 183 Northumbrian Water works, where 1 spilled longest.

Works size: 27,801 population equivalent (BIRTLEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBirtley STW6 spills, 56.3 h, 5 Jan to 8 Jan16 spills, 15.4 h, 27 Jan to 28 Jan4 spills, 7.1 h, 11 Feb to 12 Feb19 Jul 2025 18:12 GMT, 3.3 h20 Sep 2025 13:41 GMT, 15.5 h20 Oct 2025 00:01 GMT, 3 h9 spills, 31.1 h, 13 Nov to 14 Nov4 spills, 0.4 h, 15 Nov to 15 Nov3 spills, 13.3 h, 19 Nov to 19 Nov24 Nov 2025 08:15 GMT, 7.4 h29 Nov 2025 16:12 GMT, 10.2 h2 spills, 2.1 h, 1 Dec to 1 Dec2 spills, 3.4 h, 7 Dec to 7 Dec5 spills, 5.1 h, 9 Dec to 9 DecBirtley STW12 spills, 27.7 h, 5 Jan to 6 Jan9 spills, 1.5 h, 26 Jan to 27 Jan2 spills, 0.3 h, 14 Jun to 14 Jun2 spills, 0.6 h, 14 Jul to 14 Jul7 spills, 3.9 h, 19 Jul to 19 Jul16 spills, 12.9 h, 20 Sep to 21 Sep2 spills, 0.6 h, 3 Oct to 3 Oct47 spills, 1.5 h, 19 Oct to 20 Oct47 spills, 13.3 h, 11 Nov to 14 Nov23 spills, 2.5 h, 18 Nov to 19 Nov12 spills, 1.5 h, 24 Nov to 24 Nov8 spills, 1.4 h, 28 Nov to 28 Nov9 spills, 5.1 h, 29 Nov to 29 Nov11 spills, 0.2 h, 5 Dec to 5 Dec38 spills, 1.4 h, 7 Dec to 7 Dec11 spills, 0.2 h, 9 Dec to 9 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

050k100k150kJan 2025: 101 h spilling ≈ 48,017 m³ (range 19,126-120,547 m³)JanFeb 2025: 7.1 h spilling ≈ 3,382 m³ (range 1,347-8,491 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.3 h spilling ≈ 143 m³ (range 57-359 m³)JunJul 2025: 7.8 h spilling ≈ 3,716 m³ (range 1,480-9,328 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 28 h spilling ≈ 13,528 m³ (range 5,389-33,964 m³)SepOct 2025: 5.1 h spilling ≈ 2,429 m³ (range 968-6,099 m³)OctNov 2025: 86 h spilling ≈ 41,014 m³ (range 16,337-102,968 m³)NovDec 2025: 12 h spilling ≈ 5,907 m³ (range 2,353-14,829 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 14:05Birtley STW1.8 days8,096 - 51,025 m³
5 Jan 2025, 14:02Birtley STW1.1 days4,968 - 31,313 m³
20 Sep 2025, 13:41Birtley STW15.5 h2,935 - 18,497 m³
7 Jan 2025, 10:37Birtley STW12.8 h2,432 - 15,328 m³
20 Sep 2025, 13:45Birtley STW12.0 h2,283 - 14,391 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate117,660 m³range 46,866 - 295,389 m³
In litres117.7 millionrange 46.9 million - 295.4 million L
Olympic swimming pools47at 2,500 m³ each
Organic load, as people's raw sewage176,489person-days of untreated BOD

Assumed spill rate while spilling: 52.7 - 332.2 L/s (central 132.3 L/s), from a dry-weather flow of 52.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,875 kg10,589 kg59,078 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 4,921 kg50,005 kg212,975 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 89 kg741 kg2,747 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 56 kg306 kg1,595 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 4.7 trillion organisms117.7 trillion organisms3.0 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Birtley STW

Storm tank at sewage works · discharges to Team

Spills 2025
23 (173 hours) · down 57% on 2024
Spills 2024
53 (545 hours)
Long-term average
36.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Team from Source to Tyne (GB103023075670)
Outlet location
NZ2603056630 (OS grid reference) · View on Apple Maps
EA ID / permit
NWL00134 · 235/1891

Birtley STW

Inlet overflow at sewage works · discharges to Team

Spills 2025
21 (74 hours) · down 53% on 2024
Spills 2024
45 (177 hours)
Long-term average
36.0 spills a year (monitored since 2022)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Team from Source to Tyne (GB103023075670)
Outlet location
NZ2604056690 (OS grid reference) · View on Apple Maps
EA ID / permit
NWL00133 · 235/1891

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Northumbrian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.