Storm overflow register · Northumbrian Water

Falstone And Stannersburn Ps sewage works: storm overflow spills 2025

Falstone And Stannersburn Ps sewage treatment works, run by Northumbrian Water, has 1 monitored storm overflow discharging to North Tyne. In 2025 it recorded 48 spills totalling 113 hours, against 21 spills and 127 hours in 2024. By hours spilling, it ranks 119 of 183 Northumbrian Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFalstone and…1 Jan 2025 00:40 GMT, 43 min1 Jan 2025 01:35 GMT, 8.2 h1 Jan 2025 09:50 GMT, 19 min1 Jan 2025 10:10 GMT, 8 min1 Jan 2025 11:11 GMT, 29 min26 Jan 2025 01:44 GMT, 25 min26 Jan 2025 02:12 GMT, 8 min20 Feb 2025 00:41 GMT, 6 min22 Mar 2025 21:16 GMT, 1 min24 May 2025 16:12 GMT, 5 min25 May 2025 02:39 GMT, 6 min25 May 2025 16:52 GMT, 10 min25 May 2025 18:41 GMT, 4 min25 May 2025 18:53 GMT, 1 min26 May 2025 22:05 GMT, 10 min29 May 2025 06:33 GMT, 5.4 h29 May 2025 14:49 GMT, 47 min30 May 2025 00:30 GMT, 59 min31 May 2025 17:11 GMT, 1 min1 Jun 2025 13:37 GMT, 8 min3 Jun 2025 02:56 GMT, 7 min3 Jun 2025 03:27 GMT, 2 min3 Jun 2025 17:21 GMT, 5 min3 Jun 2025 20:54 GMT, 4 min4 Jun 2025 12:33 GMT, 3 min8 Jun 2025 11:25 GMT, 2 min9 Jun 2025 13:57 GMT, 67 min14 Jun 2025 00:46 GMT, 16 min14 Jun 2025 02:08 GMT, 6 min21 Jun 2025 22:04 GMT, 3 min21 Jun 2025 22:23 GMT, 13 min21 Jun 2025 22:47 GMT, 24 min21 Jun 2025 23:27 GMT, 2 min22 Jun 2025 15:57 GMT, 1 min22 Jun 2025 21:13 GMT, 1 min28 Jun 2025 03:04 GMT, 2 min28 Jun 2025 04:26 GMT, 2 min28 Jun 2025 04:30 GMT, 1 min28 Jun 2025 04:31 GMT, 1 min28 Jun 2025 04:32 GMT, 1 min28 Jun 2025 04:32 GMT, 1 min28 Jun 2025 04:33 GMT, 1 min28 Jun 2025 04:35 GMT, 1 min28 Jun 2025 07:28 GMT, 2 min1 Jul 2025 15:49 GMT, 6 min2 Jul 2025 13:28 GMT, 2 min2 Jul 2025 13:30 GMT, 3 min2 Jul 2025 13:55 GMT, 4 min2 Jul 2025 14:01 GMT, 5 min7 Jul 2025 19:45 GMT, 4 min14 Jul 2025 07:12 GMT, 9 min14 Jul 2025 07:25 GMT, 4 min14 Jul 2025 07:31 GMT, 2 min14 Jul 2025 12:10 GMT, 26 min21 Jul 2025 17:16 GMT, 13 min21 Jul 2025 18:15 GMT, 9 min30 Aug 2025 22:40 GMT, 4 min2 Sep 2025 13:15 GMT, 3 min3 Sep 2025 06:43 GMT, 5 min3 Sep 2025 12:35 GMT, 3 min3 Sep 2025 15:19 GMT, 2 min3 Sep 2025 15:22 GMT, 3 min3 Sep 2025 15:49 GMT, 6 min11 Sep 2025 03:07 GMT, 1 min11 Sep 2025 08:35 GMT, 1 min11 Sep 2025 13:00 GMT, 6 min11 Sep 2025 16:11 GMT, 1 min11 Sep 2025 17:11 GMT, 2 min12 Sep 2025 12:41 GMT, 3 min13 Sep 2025 13:36 GMT, 8 min13 Sep 2025 13:55 GMT, 3 min14 Sep 2025 17:18 GMT, 2 min15 Sep 2025 03:02 GMT, 7 min15 Sep 2025 03:32 GMT, 3 min15 Sep 2025 03:42 GMT, 3 min18 Sep 2025 20:20 GMT, 4 min18 Sep 2025 20:26 GMT, 2 min19 Sep 2025 10:47 GMT, 3 min22 Sep 2025 09:38 GMT, 2 min3 Oct 2025 01:21 GMT, 8.2 h3 Oct 2025 12:56 GMT, 14.6 h4 Oct 2025 06:43 GMT, 70 min4 Oct 2025 08:05 GMT, 5 min29 Oct 2025 00:51 GMT, 2 min1 Nov 2025 01:49 GMT, 8 min1 Nov 2025 02:22 GMT, 1 min1 Nov 2025 05:31 GMT, 2 min4 Nov 2025 08:26 GMT, 11 min4 Nov 2025 08:39 GMT, 9 min4 Nov 2025 08:56 GMT, 2 min4 Nov 2025 10:06 GMT, 13 min13 Nov 2025 05:26 GMT, 4 min23 Nov 2025 06:47 GMT, 3 min23 Nov 2025 15:56 GMT, 18 min7 Dec 2025 16:30 GMT, 4 min7 Dec 2025 16:35 GMT, 4 min7 Dec 2025 17:46 GMT, 3 min7 Dec 2025 19:27 GMT, 2.4 h7 Dec 2025 21:54 GMT, 39 min7 Dec 2025 22:34 GMT, 2 min9 Dec 2025 04:26 GMT, 5 min9 Dec 2025 06:00 GMT, 2 min9 Dec 2025 06:10 GMT, 2 min9 Dec 2025 06:12 GMT, 2 min9 Dec 2025 06:20 GMT, 1 min9 Dec 2025 06:21 GMT, 1 min9 Dec 2025 06:24 GMT, 10 min9 Dec 2025 07:30 GMT, 14 min9 Dec 2025 08:02 GMT, 18 min9 Dec 2025 09:03 GMT, 8 min9 Dec 2025 11:21 GMT, 3.7 h9 Dec 2025 15:05 GMT, 12 min9 Dec 2025 15:23 GMT, 14 min9 Dec 2025 15:47 GMT, 13 min9 Dec 2025 16:02 GMT, 7 min9 Dec 2025 16:18 GMT, 6 min9 Dec 2025 16:29 GMT, 3 min10 Dec 2025 06:01 GMT, 2.3 h10 Dec 2025 09:03 GMT, 15 min10 Dec 2025 12:02 GMT, 116 min10 Dec 2025 17:48 GMT, 10 min10 Dec 2025 17:59 GMT, 3.1 h18 Dec 2025 19:57 GMT, 1 min18 Dec 2025 20:02 GMT, 5 min18 Dec 2025 20:09 GMT, 47.1 h20 Dec 2025 19:16 GMT, 2 min

Hours spilling by month, 2025

020406080Jan 2025: 10 hours spillingJanFeb 2025: 0.1 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 7.8 hours spillingMayJun 2025: 2.9 hours spillingJunJul 2025: 1.4 hours spillingJulAug 2025: 0.1 hours spillingAugSep 2025: 1.2 hours spillingSepOct 2025: 24 hours spillingOctNov 2025: 1.2 hours spillingNovDec 2025: 64 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
18 Dec 2025, 20:09Falstone and Stannersburn PS2.0 days
3 Oct 2025, 12:56Falstone and Stannersburn PS14.6 h
3 Oct 2025, 01:21Falstone and Stannersburn PS8.2 h
1 Jan 2025, 01:35Falstone and Stannersburn PS8.2 h
29 May 2025, 06:33Falstone and Stannersburn PS5.4 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate1,936 m³range 771 – 4,861 m³
In litres1.9 millionrange 771,225 – 4.9 million L
Olympic swimming pools0.8at 2,500 m³ each
Organic load, as people's raw sewage2,904person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 31 kg174 kg972 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 81 kg823 kg3,505 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1.5 kg12 kg45 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 0.9 kg5.0 kg26 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 77.1 billion organisms1.9 trillion organisms48.6 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Falstone and Stannersburn PS

Inlet overflow at sewage works · discharges to North Tyne

Spills 2025
48 (113 hours) · up 129% on 2024
Spills 2024
21 (127 hours)
Long-term average
34.5 spills a year (monitored since 2023)
Monitor uptime
99% of the year
High-spill reason (company)
Not Applicable - Ongoing investigation
Investigation
No investigation activity in reporting period
Improvement
No improvement action in reporting period
WFD catchment
N Tyne from Lewis Burn to Tarset Burn (GB103023075070)
Outlet location
NY7238087040 (OS grid reference) · View on Apple Maps
EA ID / permit
NWL00538 · 231/A/0491

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Northumbrian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.