Storm overflow register · Northumbrian Water

Pegswood sewage works: storm overflow spills 2025

Pegswood sewage treatment works, run by Northumbrian Water, has 1 monitored storm overflow discharging to Bothal Burn. In 2025 it recorded 20 spills totalling 147 hours, against 31 spills and 252 hours in 2024. By hours spilling, it ranks 108 of 183 Northumbrian Water works, where 1 spilled longest.

Works size: 3,392 population equivalent (PEGSWOOD STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecPegswood STW5 Jan 2025 17:53 GMT, 26.5 h2 Jul 2025 15:41 GMT, 57 min20 Sep 2025 18:20 GMT, 6.3 h3 Oct 2025 15:11 GMT, 53 min2 spills, 3.2 h, 19 Oct to 20 Oct6 spills, 13 h, 13 Nov to 13 Nov8 spills, 0.9 h, 19 Nov to 19 Nov186 spills, 47.1 h, 23 Nov to 26 Nov276 spills, 8 h, 29 Nov to 30 Nov217 spills, 12.5 h, 1 Dec to 2 Dec733 spills, 39.9 h, 7 Dec to 10 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

05,00010k15kJan 2025: 27 h spilling ≈ 1,540 m³ (range 613-3,867 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.9 h spilling ≈ 52 m³ (range 21-131 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 6.3 h spilling ≈ 366 m³ (range 146-919 m³)SepOct 2025: 4.1 h spilling ≈ 238 m³ (range 95-598 m³)OctNov 2025: 69 h spilling ≈ 4,004 m³ (range 1,595-10,053 m³)NovDec 2025: 53 h spilling ≈ 3,051 m³ (range 1,215-7,660 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 17:53Pegswood STW1.1 days613 - 3,867 m³
25 Nov 2025, 05:49Pegswood STW10.1 h233 - 1,469 m³
24 Nov 2025, 18:32Pegswood STW8.9 h206 - 1,299 m³
7 Dec 2025, 15:59Pegswood STW8.5 h197 - 1,240 m³
13 Nov 2025, 06:08Pegswood STW8.4 h194 - 1,226 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate8,544 m³range 3,403 - 21,449 m³
In litres8.5 millionrange 3.4 million - 21.4 million L
Olympic swimming pools3.4at 2,500 m³ each
Organic load, as people's raw sewage12,815person-days of untreated BOD

Assumed spill rate while spilling: 6.4 - 40.5 L/s (central 16.1 L/s), from a dry-weather flow of 6.4 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 136 kg769 kg4,290 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 357 kg3,631 kg15,465 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 6.5 kg54 kg199 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 4.1 kg22 kg116 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 340.3 billion organisms8.5 trillion organisms214.5 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Pegswood STW

Storm tank at sewage works · discharges to Bothal Burn

Spills 2025
20 (147 hours) · down 35% on 2024
Spills 2024
31 (252 hours)
Long-term average
21.3 spills a year (monitored since 2020)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Bothal Burn Catchment (trib of Wansbeck) (GB103022077030)
Outlet location
NZ2337187452 (OS grid reference) · View on Apple Maps
EA ID / permit
NWL01019 · 225/1079

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Northumbrian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.