Storm overflow register · Northumbrian Water

Wooler sewage works: storm overflow spills 2025

Wooler sewage treatment works, run by Northumbrian Water, has 1 monitored storm overflow discharging to Wooler Water. In 2025 it recorded 68 spills totalling 110 hours, against 85 spills and 207 hours in 2024. By hours spilling, it ranks 120 of 183 Northumbrian Water works, where 1 spilled longest.

Works size: 3,016 population equivalent (WOOLER STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecWooler STW1 Jan 2025 11:14 GMT, 3.6 h19 spills, 7.4 h, 5 Jan to 6 Jan24 Jan 2025 03:21 GMT, 112 min3 spills, 3.9 h, 26 Jan to 27 Jan2 spills, 0.2 h, 8 Feb to 8 Feb2 spills, 0.4 h, 9 Feb to 9 Feb11 Feb 2025 08:04 GMT, 8 min2 spills, 0.2 h, 20 Feb to 20 Feb2 spills, 0 h, 24 Feb to 24 Feb2 spills, 0.9 h, 12 Mar to 13 Mar2 spills, 2.5 h, 22 Mar to 22 Mar6 spills, 0.9 h, 16 Apr to 16 Apr7 spills, 1.1 h, 23 May to 24 May26 May 2025 22:04 GMT, 67 min2 spills, 0.7 h, 1 Jun to 2 Jun3 Jun 2025 13:42 GMT, 2 min2 spills, 1.5 h, 7 Jun to 7 Jun8 Jun 2025 16:46 GMT, 21 min5 spills, 0.4 h, 9 Jun to 10 Jun2 spills, 0.7 h, 14 Jun to 14 Jun21 Jun 2025 23:21 GMT, 77 min3 spills, 0.3 h, 22 Jun to 22 Jun12 spills, 5.1 h, 1 Jul to 2 Jul7 Jul 2025 18:06 GMT, 55 min2 spills, 1.1 h, 14 Jul to 14 Jul12 spills, 4.1 h, 19 Jul to 20 Jul20 Jul 2025 23:33 GMT, 3 min2 spills, 0.3 h, 31 Jul to 31 Jul2 spills, 0.8 h, 4 Aug to 4 Aug2 spills, 0 h, 11 Aug to 11 Aug5 spills, 2.3 h, 3 Sep to 3 Sep2 spills, 2 h, 10 Sep to 10 Sep13 Sep 2025 14:42 GMT, 19 min8 spills, 2.2 h, 14 Sep to 15 Sep19 Sep 2025 11:38 GMT, 3 min10 spills, 4 h, 20 Sep to 20 Sep3 spills, 3.4 h, 3 Oct to 3 Oct9 spills, 4.8 h, 19 Oct to 20 Oct8 spills, 2.2 h, 23 Oct to 23 Oct17 spills, 5.8 h, 24 Oct to 24 Oct27 Oct 2025 02:17 GMT, 71 min29 Oct 2025 01:25 GMT, 14 min3 spills, 1.2 h, 1 Nov to 1 Nov10 Nov 2025 20:10 GMT, 26 min17 spills, 10.6 h, 13 Nov to 13 Nov8 spills, 5.2 h, 18 Nov to 19 Nov8 spills, 1.4 h, 20 Nov to 20 Nov12 spills, 5.7 h, 23 Nov to 25 Nov5 spills, 4.6 h, 29 Nov to 29 Nov7 spills, 2.2 h, 30 Nov to 1 Dec5 spills, 3 h, 5 Dec to 6 Dec8 spills, 4 h, 7 Dec to 7 Dec4 spills, 1.9 h, 9 Dec to 9 Dec18 Dec 2025 17:29 GMT, 2 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

01,0002,0003,0004,000Jan 2025: 17 h spilling ≈ 863 m³ (range 344-2,167 m³)JanFeb 2025: 0.9 h spilling ≈ 47 m³ (range 19-117 m³)FebMar 2025: 3.3 h spilling ≈ 171 m³ (range 68-428 m³)MarApr 2025: 0.9 h spilling ≈ 47 m³ (range 19-117 m³)AprMay 2025: 2.2 h spilling ≈ 114 m³ (range 45-285 m³)MayJun 2025: 5.3 h spilling ≈ 274 m³ (range 109-688 m³)JunJul 2025: 12 h spilling ≈ 594 m³ (range 237-1,492 m³)JulAug 2025: 0.8 h spilling ≈ 41 m³ (range 16-104 m³)AugSep 2025: 11 h spilling ≈ 558 m³ (range 222-1,401 m³)SepOct 2025: 18 h spilling ≈ 910 m³ (range 362-2,283 m³)OctNov 2025: 29 h spilling ≈ 1,519 m³ (range 605-3,814 m³)NovDec 2025: 11 h spilling ≈ 568 m³ (range 226-1,427 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
13 Nov 2025, 03:05Wooler STW5.8 h120 - 757 m³
29 Nov 2025, 10:18Wooler STW3.8 h79 - 495 m³
18 Nov 2025, 20:28Wooler STW3.6 h73 - 463 m³
1 Jan 2025, 11:14Wooler STW3.6 h73 - 463 m³
3 Oct 2025, 13:48Wooler STW3.2 h66 - 417 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate5,705 m³range 2,272 - 14,323 m³
In litres5.7 millionrange 2.3 million - 14.3 million L
Olympic swimming pools2.3at 2,500 m³ each
Organic load, as people's raw sewage8,558person-days of untreated BOD

Assumed spill rate while spilling: 5.7 - 36.0 L/s (central 14.4 L/s), from a dry-weather flow of 5.7 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 91 kg513 kg2,865 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 239 kg2,425 kg10,327 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 4.3 kg36 kg133 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 2.7 kg15 kg77 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 227.2 billion organisms5.7 trillion organisms143.2 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Wooler STW

Inlet overflow at sewage works · discharges to Wooler Water

Spills 2025
68 (110 hours) · down 20% on 2024
Spills 2024
85 (207 hours)
Long-term average
63.5 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Env Act (SODRP) investigation ongoing, Operational investigation ongoing
Improvement
Operational improvement ongoing
WFD catchment
Wooler Water from Harthope Burn to Till (GB102021072930)
Outlet location
NT9990629453 (OS grid reference) · View on Apple Maps
EA ID / permit
NWL01553 · 210/1275

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Northumbrian Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.