Storm overflow register · Severn Trent Water

Armthorpe sewage works: storm overflow spills 2025

Armthorpe sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Tributary of the Fores Drain. In 2025 it recorded 19 spills totalling 61 hours, against 12 spills and 40 hours in 2024. By hours spilling, it ranks 308 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 14,856 population equivalent (ARMTHORPE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecArmthorpe Sewage…5 Jan 2025 17:11 GMT, 11.9 h6 Jan 2025 05:25 GMT, 6.9 h27 Jan 2025 05:43 GMT, 11 min19 Jul 2025 14:58 GMT, 68 min20 Jul 2025 14:58 GMT, 22 min20 Jul 2025 16:57 GMT, 25 min3 Sep 2025 15:59 GMT, 34 min3 Sep 2025 17:27 GMT, 17 min17 Sep 2025 08:25 GMT, 17 min20 Sep 2025 18:29 GMT, 50 min20 Sep 2025 19:39 GMT, 6.5 h10 Nov 2025 18:14 GMT, 58 min12 Nov 2025 20:44 GMT, 54 min14 Nov 2025 10:40 GMT, 40 min14 Nov 2025 11:40 GMT, 2.8 h14 Nov 2025 14:49 GMT, 16 min14 Nov 2025 15:25 GMT, 9.8 h15 Nov 2025 02:09 GMT, 58 min15 Nov 2025 07:46 GMT, 80 min15 Nov 2025 12:09 GMT, 12 min15 Nov 2025 13:10 GMT, 24 min23 Nov 2025 20:29 GMT, 25 min29 Nov 2025 07:44 GMT, 39 min29 Nov 2025 08:35 GMT, 17 min29 Nov 2025 10:10 GMT, 41 min29 Nov 2025 12:57 GMT, 58 min29 Nov 2025 15:03 GMT, 79 min29 Nov 2025 20:19 GMT, 2.6 h4 Dec 2025 19:13 GMT, 96 min4 Dec 2025 21:55 GMT, 10 min4 Dec 2025 22:25 GMT, 10 min9 Dec 2025 08:15 GMT, 25 min9 Dec 2025 10:08 GMT, 51 min15 Dec 2025 19:44 GMT, 71 min18 Dec 2025 16:28 GMT, 76 min18 Dec 2025 18:10 GMT, 29 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

05,00010k15k20kJan 2025: 19 h spilling ≈ 4,836 m³ (range 1,926–12,142 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 1.9 h spilling ≈ 484 m³ (range 193–1,214 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 8.5 h spilling ≈ 2,164 m³ (range 862–5,432 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 25 h spilling ≈ 6,389 m³ (range 2,545–16,040 m³)NovDec 2025: 6.1 h spilling ≈ 1,553 m³ (range 618–3,898 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 17:11Armthorpe Sewage Treatment Works11.9 h1,205 – 7,594 m³
14 Nov 2025, 15:25Armthorpe Sewage Treatment Works9.8 h994 – 6,263 m³
6 Jan 2025, 05:25Armthorpe Sewage Treatment Works6.9 h701 – 4,420 m³
20 Sep 2025, 19:39Armthorpe Sewage Treatment Works6.5 h661 – 4,165 m³
14 Nov 2025, 11:40Armthorpe Sewage Treatment Works2.8 h281 – 1,768 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate15,426 m³range 6,144 – 38,727 m³
In litres15.4 millionrange 6.1 million – 38.7 million L
Olympic swimming pools6.2at 2,500 m³ each
Organic load, as people's raw sewage23,139person-days of untreated BOD

Assumed spill rate while spilling: 28.2 – 177.5 L/s (central 70.7 L/s), from a dry-weather flow of 28.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 246 kg1,388 kg7,745 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 645 kg6,556 kg27,922 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 12 kg97 kg360 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 7.4 kg40 kg209 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 614.4 billion organisms15.4 trillion organisms387.3 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Armthorpe Sewage Treatment Works

Storm tank at sewage works · discharges to Tributary of the Fores Drain

Spills 2025
19 (61 hours) · up 58% on 2024
Spills 2024
12 (40 hours)
Long-term average
27.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Hatfield Waste Drain Catchment (trib of Torne/Three Rivers) (GB104028064330)
Outlet location
SE6428004440 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00109 · T/83/45356/R · company name: ARMTHORPE STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.