Storm overflow register · Severn Trent Water

Blakeney sewage works: storm overflow spills 2025

Blakeney sewage treatment works, run by Severn Trent Water, has 3 monitored storm overflows discharging to River Severn. In 2025 they recorded 233 spills totalling 2,042 hours, against 338 spills and 3,852 hours in 2024. By hours spilling, it ranks 2 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 14,115 population equivalent (BLAKENEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecBlakeney STW (Ssto)6 spills, 15.2 h, 1 Jan to 2 Jan28 spills, 138.2 h, 5 Jan to 12 Jan2 spills, 0.9 h, 13 Jan to 13 Jan2 spills, 0.6 h, 14 Jan to 14 Jan44 spills, 215.1 h, 23 Jan to 5 Feb6 Feb 2025 21:23 GMT, 30 min12 spills, 5.3 h, 7 Feb to 9 Feb3 spills, 3.5 h, 10 Feb to 10 Feb13 Feb 2025 21:57 GMT, 37 min3 spills, 5.8 h, 15 Feb to 15 Feb8 spills, 19 h, 20 Feb to 22 Feb12 spills, 86.8 h, 23 Feb to 27 Feb1 Mar 2025 12:15 GMT, 23 min2 Mar 2025 12:25 GMT, 11 min21 Mar 2025 21:10 GMT, 106 min23 Mar 2025 02:40 GMT, 75 min18 Apr 2025 17:08 GMT, 2.6 h19 Apr 2025 23:57 GMT, 9 min2 spills, 10.5 h, 22 Apr to 23 Apr11 May 2025 17:47 GMT, 29 min2 spills, 1.6 h, 21 May to 21 May3 spills, 1.5 h, 27 May to 27 May2 spills, 2.8 h, 3 Jun to 3 Jun2 spills, 4.1 h, 5 Jun to 5 Jun7 Jun 2025 16:53 GMT, 2.9 h12 Jun 2025 12:28 GMT, 3.1 h27 Jun 2025 02:13 GMT, 6 min6 Jul 2025 13:32 GMT, 10 min15 Jul 2025 08:34 GMT, 28 min3 spills, 3.9 h, 20 Jul to 20 Jul2 spills, 2 h, 29 Jul to 29 Jul4 spills, 2 h, 31 Jul to 31 Jul3 spills, 1.1 h, 29 Aug to 29 Aug30 Aug 2025 15:30 GMT, 6.1 h31 Aug 2025 16:47 GMT, 95 min6 spills, 13.8 h, 3 Sep to 4 Sep6 spills, 10.4 h, 7 Sep to 8 Sep16 spills, 30.4 h, 10 Sep to 15 Sep6 spills, 3 h, 17 Sep to 18 Sep4 spills, 10.8 h, 3 Oct to 3 Oct10 spills, 26.2 h, 19 Oct to 20 Oct6 spills, 10.1 h, 22 Oct to 23 Oct8 spills, 11.5 h, 24 Oct to 26 Oct7 spills, 12.2 h, 29 Oct to 29 Oct30 Oct 2025 23:51 GMT, 2.5 h5 spills, 6.1 h, 31 Oct to 1 Nov2 spills, 0.5 h, 3 Nov to 3 Nov9 spills, 31.7 h, 4 Nov to 5 Nov2 spills, 5.4 h, 7 Nov to 8 Nov49 spills, 233.8 h, 9 Nov to 21 Nov26 spills, 30.8 h, 22 Nov to 24 Nov26 Nov 2025 18:55 GMT, 6 min43 spills, 595.7 h, 29 Nov to 27 Dec4 spills, 1.4 h, 28 Dec to 28 Dec6 spills, 0.8 h, 29 Dec to 30 Dec2 spills, 0.3 h, 31 Dec to 31 DecBlakeney Sewage…1 Jan 2025 07:53 GMT, 7.3 h5 spills, 67.8 h, 5 Jan to 8 Jan2 spills, 15 h, 23 Jan to 24 Jan10 spills, 86 h, 26 Jan to 31 Jan4 Feb 2025 16:30 GMT, 21 min13 Feb 2025 21:52 GMT, 16 min2 spills, 1.3 h, 15 Feb to 15 Feb20 Feb 2025 10:11 GMT, 84 min2 spills, 4.5 h, 21 Feb to 21 Feb7 spills, 32.8 h, 23 Feb to 25 Feb3 spills, 2.3 h, 26 Feb to 26 Feb23 Mar 2025 02:32 GMT, 26 min18 Apr 2025 17:19 GMT, 108 min19 Apr 2025 23:55 GMT, 10 min22 Apr 2025 23:25 GMT, 6.7 h2 spills, 0.2 h, 21 May to 21 May3 spills, 0.9 h, 5 Jun to 5 Jun2 spills, 1.4 h, 7 Jun to 7 Jun4 spills, 2.1 h, 12 Jun to 12 Jun2 spills, 1 h, 20 Jul to 20 Jul2 spills, 0.7 h, 31 Jul to 31 Jul4 spills, 1.4 h, 30 Aug to 30 Aug4 spills, 2.2 h, 3 Sep to 4 Sep6 spills, 2.1 h, 7 Sep to 7 Sep3 spills, 1.4 h, 10 Sep to 11 Sep2 spills, 1.1 h, 13 Sep to 13 Sep5 spills, 4.2 h, 14 Sep to 14 Sep5 spills, 3.1 h, 3 Oct to 3 Oct10 spills, 6.5 h, 19 Oct to 19 Oct3 spills, 3 h, 22 Oct to 23 Oct2 spills, 0.6 h, 24 Oct to 24 Oct2 spills, 1.9 h, 29 Oct to 29 Oct2 spills, 0.9 h, 30 Oct to 31 Oct31 Oct 2025 23:11 GMT, 87 min8 spills, 5.4 h, 4 Nov to 5 Nov12 spills, 6 h, 9 Nov to 10 Nov85 spills, 58.5 h, 11 Nov to 16 Nov6 spills, 4.2 h, 29 Nov to 29 Nov16 spills, 6.7 h, 1 Dec to 2 Dec80 spills, 60.6 h, 5 Dec to 11 Dec5 spills, 3.3 h, 12 Dec to 12 Dec91 spills, 42.8 h, 15 Dec to 22 DecBlakeney Sewage…14 Nov 2025 14:54 GMT, 9.7 h2 spills, 1.4 h, 15 Dec to 15 Dec19 Dec 2025 04:26 GMT, 20 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0200k400k600kJan 2025: 498 h spilling ≈ 120,346 m³ (range 47,936-302,133 m³)JanFeb 2025: 213 h spilling ≈ 51,490 m³ (range 20,510-129,269 m³)FebMar 2025: 4.0 h spilling ≈ 967 m³ (range 385-2,429 m³)MarApr 2025: 22 h spilling ≈ 5,297 m³ (range 2,110-13,297 m³)AprMay 2025: 3.7 h spilling ≈ 895 m³ (range 356-2,247 m³)MayJun 2025: 17 h spilling ≈ 4,208 m³ (range 1,676-10,565 m³)JunJul 2025: 10 h spilling ≈ 2,491 m³ (range 992-6,254 m³)JulAug 2025: 10 h spilling ≈ 2,443 m³ (range 973-6,133 m³)AugSep 2025: 69 h spilling ≈ 16,591 m³ (range 6,609-41,653 m³)SepOct 2025: 92 h spilling ≈ 22,226 m³ (range 8,853-55,800 m³)OctNov 2025: 411 h spilling ≈ 99,305 m³ (range 39,555-249,308 m³)NovDec 2025: 694 h spilling ≈ 167,749 m³ (range 66,818-421,140 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
1 Dec 2025, 04:12Blakeney STW (Ssto)12.9 days29,918 - 188,570 m³
15 Dec 2025, 04:40Blakeney STW (Ssto)8.9 days20,590 - 129,775 m³
11 Nov 2025, 18:52Blakeney STW (Ssto)5.5 days12,639 - 79,662 m³
26 Jan 2025, 11:48Blakeney STW (Ssto)3.9 days9,009 - 56,781 m³
6 Jan 2025, 06:08Blakeney STW (Ssto)2.6 days6,112 - 38,526 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate493,960 m³range 196,754 - 1.2 million m³
In litres494.0 millionrange 196.8 million - 1.2 billion L
Olympic swimming pools198at 2,500 m³ each
Organic load, as people's raw sewage740,939person-days of untreated BOD

Assumed spill rate while spilling: 26.8 - 168.7 L/s (central 67.2 L/s), from a dry-weather flow of 26.8 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 7,870 kg44,456 kg248,021 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 20,659 kg209,933 kg894,116 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 374 kg3,112 kg11,533 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 236 kg1,284 kg6,697 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 19.7 trillion organisms494.0 trillion organisms1.2 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Blakeney STW (Ssto)

Storm tank at sewage works · discharges to River Severn

Spills 2025
153 (1,579 hours) · down 22% on 2024
Spills 2024
197 (2,807 hours)
Long-term average
128.5 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Severn River and Trib Estuary (GB530905415403)
Outlet location
SO6911006040 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00291 · S/20/26262/R · company name: BLAKENEY (STW)

Blakeney Sewage Treatment Works

Inlet overflow at sewage works · discharges to River Severn

Spills 2025
77 (452 hours) · down 41% on 2024
Spills 2024
130 (961 hours)
Long-term average
67.0 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Severn River and Trib Estuary (GB530905415403)
Outlet location
SO6911006040 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00289 · S/20/26262/R · company name: BLAKENEY STW STAGE 2 SPS (CSO)

Blakeney Sewage Treatment Works

Inlet overflow at sewage works · discharges to River Severn

Spills 2025
3 (11 hours) · down 73% on 2024
Spills 2024
11 (84 hours)
Long-term average
37.8 spills a year (monitored since 2022)
Monitor uptime
100% of the year
Investigation
UWWTR investigation completed, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Severn River and Trib Estuary (GB530905415403)
Outlet location
SO6911006040 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00290 · S/20/26262/R · company name: BLAKENEY STW STAGE 1 SPS (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.