Storm overflow register · Severn Trent Water

Colwall sewage works: storm overflow spills 2025

Colwall sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Cradley Brook. In 2025 it recorded 81 spills totalling 799 hours, against 143 spills and 1,947 hours in 2024. By hours spilling, it ranks 40 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 2,179 population equivalent (COLWALL STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecColwall Sewage…3 spills, 10.5 h, 1 Jan to 2 Jan13 spills, 100.2 h, 5 Jan to 10 Jan20 Jan 2025 10:40 GMT, 41 min6 spills, 15.3 h, 23 Jan to 25 Jan20 spills, 105.6 h, 26 Jan to 2 Feb3 Feb 2025 08:25 GMT, 20 min4 Feb 2025 15:15 GMT, 95 min2 spills, 2.1 h, 8 Feb to 9 Feb8 spills, 17.7 h, 10 Feb to 11 Feb12 Feb 2025 13:38 GMT, 11 min2 spills, 0.6 h, 13 Feb to 13 Feb5 spills, 20.9 h, 15 Feb to 16 Feb18 Feb 2025 10:25 GMT, 25 min21 spills, 78.1 h, 21 Feb to 27 Feb23 Apr 2025 04:26 GMT, 9.6 h7 Sep 2025 12:53 GMT, 5 h8 Sep 2025 18:08 GMT, 87 min11 Sep 2025 22:23 GMT, 12 min14 Sep 2025 17:38 GMT, 5.4 h2 spills, 2.9 h, 3 Oct to 3 Oct19 Oct 2025 17:53 GMT, 5.2 h4 Nov 2025 21:38 GMT, 3.7 h10 Nov 2025 14:42 GMT, 2.3 h2 spills, 24.8 h, 11 Nov to 13 Nov50 spills, 71.5 h, 14 Nov to 18 Nov9 spills, 23.3 h, 22 Nov to 23 Nov2 spills, 21.5 h, 28 Nov to 30 Nov16 spills, 234.3 h, 1 Dec to 13 Dec8 spills, 3.9 h, 15 Dec to 16 Dec11 spills, 4.4 h, 17 Dec to 18 Dec50 spills, 25.1 h, 21 Dec to 23 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30kJan 2025: 228 h spilling ≈ 8,520 m³ (range 3,394-21,390 m³)JanFeb 2025: 126 h spilling ≈ 4,701 m³ (range 1,872-11,801 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 9.6 h spilling ≈ 358 m³ (range 143-900 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 12 h spilling ≈ 452 m³ (range 180-1,134 m³)SepOct 2025: 8.1 h spilling ≈ 302 m³ (range 120-759 m³)OctNov 2025: 147 h spilling ≈ 5,488 m³ (range 2,186-13,779 m³)NovDec 2025: 268 h spilling ≈ 9,991 m³ (range 3,980-25,083 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 03:10Colwall Sewage Treatment Works3.9 days1,386 - 8,736 m³
26 Jan 2025, 12:25Colwall Sewage Treatment Works3.6 days1,270 - 8,006 m³
5 Dec 2025, 15:18Colwall Sewage Treatment Works3.3 days1,179 - 7,430 m³
9 Dec 2025, 01:10Colwall Sewage Treatment Works2.9 days1,025 - 6,460 m³
1 Dec 2025, 17:10Colwall Sewage Treatment Works1.8 days627 - 3,952 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate29,824 m³range 11,879 - 74,874 m³
In litres29.8 millionrange 11.9 million - 74.9 million L
Olympic swimming pools12at 2,500 m³ each
Organic load, as people's raw sewage44,736person-days of untreated BOD

Assumed spill rate while spilling: 4.1 - 26.0 L/s (central 10.4 L/s), from a dry-weather flow of 4.1 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 475 kg2,684 kg14,975 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,247 kg12,675 kg53,984 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 23 kg188 kg696 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 14 kg78 kg404 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.2 trillion organisms29.8 trillion organisms748.7 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Colwall Sewage Treatment Works

Storm tank at sewage works · discharges to Cradley Brook

Spills 2025
81 (799 hours) · down 43% on 2024
Spills 2024
143 (1,947 hours)
Long-term average
103.4 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Cradley Bk - source to conf Suckley Bk (GB109054039910)
Outlet location
SO7367842954 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00621 · S/09/55757/R · company name: COLWALL STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.