Storm overflow register · Severn Trent Water

Elmhurst sewage works: storm overflow spills 2025

Elmhurst sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Tributary of Full Brook. In 2025 it recorded 13 spills totalling 70 hours, against 90 spills and 1,277 hours in 2024. By hours spilling, it ranks 300 of 435 Severn Trent Water works, where 1 spilled longest.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecElmhurst Sewage…1 Jan 2025 05:59 GMT, 10 min1 Jan 2025 07:35 GMT, 3.6 h1 Jan 2025 12:20 GMT, 2.2 h1 Jan 2025 14:33 GMT, 6 min1 Jan 2025 14:40 GMT, 2.3 h5 Jan 2025 07:59 GMT, 112 min5 Jan 2025 09:56 GMT, 11.1 h6 Jan 2025 11:49 GMT, 10.3 h6 Jan 2025 22:22 GMT, 7.1 h7 Jan 2025 13:48 GMT, 2.2 h27 Jan 2025 01:00 GMT, 51 min27 Jan 2025 01:52 GMT, 7.3 h28 Jan 2025 09:36 GMT, 9.2 h31 Jan 2025 02:43 GMT, 2.2 h5 Jun 2025 10:01 GMT, 2 min19 Jul 2025 19:29 GMT, 2 min11 Nov 2025 21:39 GMT, 70 min14 Nov 2025 17:32 GMT, 113 min14 Nov 2025 20:36 GMT, 66 min18 Dec 2025 13:48 GMT, 103 min18 Dec 2025 16:28 GMT, 5 min18 Dec 2025 19:12 GMT, 9 min18 Dec 2025 19:30 GMT, 2.9 h

Hours spilling by month, 2025

020406080Jan 2025: 60 hours spillingJanFeb 2025: 0.0 hours spillingFebMar 2025: 0.0 hours spillingMarApr 2025: 0.0 hours spillingAprMay 2025: 0.0 hours spillingMayJun 2025: 0.0 hours spillingJunJul 2025: 0.0 hours spillingJulAug 2025: 0.0 hours spillingAugSep 2025: 0.0 hours spillingSepOct 2025: 0.0 hours spillingOctNov 2025: 4.2 hours spillingNovDec 2025: 4.9 hours spillingDec
Hours, measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDuration
5 Jan 2025, 09:56Elmhurst Sewage Treatment Works11.1 h
6 Jan 2025, 11:49Elmhurst Sewage Treatment Works10.3 h
28 Jan 2025, 09:36Elmhurst Sewage Treatment Works9.2 h
27 Jan 2025, 01:52Elmhurst Sewage Treatment Works7.3 h
6 Jan 2025, 22:22Elmhurst Sewage Treatment Works7.1 h

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

This works serves fewer than 2,000 people, or was not matched to a UWWTD report, so its size is not published. The population equivalent above is a placeholder of 1,000. Enter the population served if you know it.

Volume, central estimate1,191 m³range 474 – 2,990 m³
In litres1.2 millionrange 474,338 – 3.0 million L
Olympic swimming pools0.5at 2,500 m³ each
Organic load, as people's raw sewage1,786person-days of untreated BOD

Assumed spill rate while spilling: 1.9 – 11.9 L/s (central 4.8 L/s), from a dry-weather flow of 1.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 19 kg107 kg598 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 50 kg506 kg2,156 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 0.9 kg7.5 kg28 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 0.6 kg3.1 kg16 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 47.4 billion organisms1.2 trillion organisms29.9 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Elmhurst Sewage Treatment Works

Inlet overflow at sewage works · discharges to Tributary of Full Brook

Spills 2025
13 (70 hours) · down 86% on 2024
Spills 2024
90 (1,277 hours)
Long-term average
78.8 spills a year (monitored since 2020)
Monitor uptime
98% of the year
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Pyford Brook Catchment (trib of Trent) (GB104028047250)
Outlet location
SK1159112248 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00861 · T/07/35741/R · company name: NASH LANE - ELMHURST STW (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.