Storm overflow register · Severn Trent Water

Farnsfield sewage works: storm overflow spills 2025

Farnsfield sewage treatment works, run by Severn Trent Water, has 2 monitored storm overflows discharging to Cotton Mill Dyke, Trib R Greet. In 2025 they recorded 31 spills totalling 70 hours, against 52 spills and 166 hours in 2024. By hours spilling, it ranks 299 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 3,201 population equivalent (FARNSFIELD STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFarnsfield Sewage…5 Jan 2025 21:36 GMT, 2.5 h6 Jan 2025 03:10 GMT, 3.4 h6 Jan 2025 08:55 GMT, 65 min17 Sep 2025 07:51 GMT, 2.5 h21 Sep 2025 01:13 GMT, 37 min4 Nov 2025 21:43 GMT, 51 min14 Nov 2025 07:56 GMT, 27.9 h29 Nov 2025 10:25 GMT, 25 min29 Nov 2025 11:25 GMT, 85 min29 Nov 2025 21:22 GMT, 103 min9 Dec 2025 07:10 GMT, 99 min9 Dec 2025 13:10 GMT, 10 min18 Dec 2025 16:26 GMT, 4.9 h18 Dec 2025 21:40 GMT, 10 minFarnsfield Sewage…1 Jan 2025 07:34 GMT, 26 min1 Jan 2025 08:09 GMT, 10 min5 Jan 2025 22:09 GMT, 2.4 h6 Jan 2025 03:15 GMT, 3 min6 Jan 2025 03:27 GMT, 45 min6 Jan 2025 04:14 GMT, 111 min6 Jan 2025 06:08 GMT, 27 min6 Jan 2025 06:40 GMT, 19 min6 Jan 2025 07:02 GMT, 5 min6 Jan 2025 07:09 GMT, 39 min6 Jan 2025 07:57 GMT, 14 min6 Jan 2025 08:14 GMT, 3 min6 Jan 2025 08:21 GMT, 12 min6 Jan 2025 08:34 GMT, 3 min6 Jan 2025 08:39 GMT, 97 min6 Jan 2025 10:24 GMT, 9 min6 Jan 2025 10:41 GMT, 4 min27 Jan 2025 01:41 GMT, 3 min27 Jan 2025 01:47 GMT, 20 min27 Jan 2025 02:12 GMT, 36 min27 Jan 2025 02:53 GMT, 5 min20 Feb 2025 16:55 GMT, 16 min20 Feb 2025 17:12 GMT, 8 min24 Feb 2025 11:47 GMT, 19 min22 Mar 2025 15:21 GMT, 1 min22 Mar 2025 15:29 GMT, 18 min22 Mar 2025 15:48 GMT, 25 min22 Mar 2025 16:28 GMT, 2 min28 Mar 2025 08:14 GMT, 3 min17 May 2025 10:14 GMT, 4.5 h19 Jul 2025 11:56 GMT, 58 min20 Jul 2025 13:58 GMT, 10 min20 Jul 2025 17:44 GMT, 4 min21 Jul 2025 14:10 GMT, 13 min3 Sep 2025 14:58 GMT, 4 min20 Sep 2025 20:01 GMT, 26 min23 Oct 2025 00:58 GMT, 7 min4 Nov 2025 19:12 GMT, 22 min4 Nov 2025 19:55 GMT, 17 min7 Nov 2025 16:14 GMT, 10 min11 Nov 2025 23:50 GMT, 15 min14 Nov 2025 08:17 GMT, 18 min14 Nov 2025 08:55 GMT, 13 min14 Nov 2025 18:55 GMT, 25 min14 Nov 2025 21:55 GMT, 10 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

02,0004,0006,000Jan 2025: 18 h spilling ≈ 965 m³ (range 385–2,423 m³)JanFeb 2025: 0.7 h spilling ≈ 38 m³ (range 15–96 m³)FebMar 2025: 0.8 h spilling ≈ 44 m³ (range 17–110 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 4.5 h spilling ≈ 247 m³ (range 98–620 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 1.4 h spilling ≈ 77 m³ (range 31–193 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 3.6 h spilling ≈ 197 m³ (range 79–496 m³)SepOct 2025: 0.1 h spilling ≈ 5.5 m³ (range 2.2–14 m³)OctNov 2025: 35 h spilling ≈ 1,892 m³ (range 754–4,751 m³)NovDec 2025: 6.9 h spilling ≈ 378 m³ (range 151–950 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 07:56Farnsfield Sewage Treatment Works1.2 days610 – 3,842 m³
18 Dec 2025, 16:26Farnsfield Sewage Treatment Works4.9 h107 – 672 m³
17 May 2025, 10:14Farnsfield Sewage Treatment Works4.5 h98 – 615 m³
6 Jan 2025, 03:10Farnsfield Sewage Treatment Works3.4 h75 – 470 m³
5 Jan 2025, 21:36Farnsfield Sewage Treatment Works2.5 h55 – 347 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate3,839 m³range 1,529 – 9,639 m³
In litres3.8 millionrange 1.5 million – 9.6 million L
Olympic swimming pools1.5at 2,500 m³ each
Organic load, as people's raw sewage5,759person-days of untreated BOD

Assumed spill rate while spilling: 6.1 – 38.2 L/s (central 15.2 L/s), from a dry-weather flow of 6.1 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 61 kg346 kg1,928 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 161 kg1,632 kg6,950 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 2.9 kg24 kg90 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1.8 kg10.0 kg52 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 152.9 billion organisms3.8 trillion organisms96.4 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Farnsfield Sewage Treatment Works

Storm tank at sewage works · discharges to Cotton Mill Dyke, Trib R Greet

Spills 2025
11 (49 hours) · down 48% on 2024
Spills 2024
21 (100 hours)
Long-term average
26.4 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Greet Catchment (trib of Trent) (GB104028053410)
Outlet location
SK6627756168 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00888 · T/64/45766/R · company name: FARNSFIELD STW (SSTO)

Farnsfield Sewage Treatment Works

Inlet overflow at sewage works · discharges to Cotton Mill Dyke, Trib R Greet

Spills 2025
20 (21 hours) · down 35% on 2024
Spills 2024
31 (66 hours)
Long-term average
36.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Greet Catchment (trib of Trent) (GB104028053410)
Outlet location
SK6627756168 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00887 · T/64/45766/R · company name: FARNSFIELD STW (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.