Storm overflow register · Severn Trent Water

Fleckney sewage works: storm overflow spills 2025

Fleckney sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Tributary of Burton Brook. In 2025 it recorded 43 spills totalling 348 hours, against 79 spills and 787 hours in 2024. By hours spilling, it ranks 117 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 5,063 population equivalent (FLECKNEY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecFleckney Sewage…1 Jan 2025 11:04 GMT, 51 min1 Jan 2025 11:58 GMT, 8 min1 Jan 2025 12:43 GMT, 2 min1 Jan 2025 12:47 GMT, 5 min5 Jan 2025 12:02 GMT, 59 min5 Jan 2025 13:02 GMT, 35 min5 Jan 2025 13:40 GMT, 79 min5 Jan 2025 15:03 GMT, 103 min5 Jan 2025 16:48 GMT, 66 min5 Jan 2025 17:56 GMT, 32.7 h7 Jan 2025 02:40 GMT, 20 min7 Jan 2025 03:00 GMT, 2.4 h7 Jan 2025 05:28 GMT, 5 min7 Jan 2025 05:50 GMT, 31 min7 Jan 2025 06:23 GMT, 28 min7 Jan 2025 06:53 GMT, 2.1 h7 Jan 2025 09:02 GMT, 2.3 h7 Jan 2025 11:24 GMT, 45 min7 Jan 2025 12:19 GMT, 8 min7 Jan 2025 12:28 GMT, 5 min7 Jan 2025 12:38 GMT, 50 min7 Jan 2025 13:32 GMT, 8 min7 Jan 2025 13:44 GMT, 3 min7 Jan 2025 13:50 GMT, 49 min7 Jan 2025 14:43 GMT, 35 min7 Jan 2025 15:25 GMT, 9 min7 Jan 2025 15:38 GMT, 5 min7 Jan 2025 15:48 GMT, 4 min7 Jan 2025 15:52 GMT, 11 min7 Jan 2025 16:11 GMT, 24 min7 Jan 2025 16:38 GMT, 26 min7 Jan 2025 17:06 GMT, 5 min7 Jan 2025 17:12 GMT, 22 min7 Jan 2025 17:37 GMT, 8 min7 Jan 2025 17:56 GMT, 12 min7 Jan 2025 18:17 GMT, 30 min7 Jan 2025 18:48 GMT, 5 min7 Jan 2025 18:54 GMT, 18 min7 Jan 2025 19:15 GMT, 65 min7 Jan 2025 20:28 GMT, 67 min7 Jan 2025 21:38 GMT, 11 min7 Jan 2025 21:50 GMT, 7 min7 Jan 2025 22:00 GMT, 10 min7 Jan 2025 22:12 GMT, 22 min7 Jan 2025 22:45 GMT, 7 min26 Jan 2025 15:03 GMT, 11 min26 Jan 2025 17:21 GMT, 39 min26 Jan 2025 22:41 GMT, 20 min27 Jan 2025 00:44 GMT, 50 min27 Jan 2025 01:49 GMT, 114 min27 Jan 2025 03:45 GMT, 6 min27 Jan 2025 03:52 GMT, 19 min27 Jan 2025 04:13 GMT, 52 min27 Jan 2025 05:07 GMT, 56 min27 Jan 2025 06:04 GMT, 55 min27 Jan 2025 07:06 GMT, 115 min27 Jan 2025 09:02 GMT, 5 min27 Jan 2025 09:08 GMT, 27 min27 Jan 2025 09:36 GMT, 17 min27 Jan 2025 09:54 GMT, 17 min27 Jan 2025 10:12 GMT, 33 min27 Jan 2025 10:50 GMT, 17 min27 Jan 2025 11:08 GMT, 5 min27 Jan 2025 21:16 GMT, 56 min27 Jan 2025 22:12 GMT, 25 min28 Jan 2025 06:10 GMT, 7 min28 Jan 2025 06:20 GMT, 2 min28 Jan 2025 06:36 GMT, 50 min28 Jan 2025 07:29 GMT, 16 min28 Jan 2025 07:46 GMT, 26 min28 Jan 2025 08:20 GMT, 26 min28 Jan 2025 08:48 GMT, 10 min28 Jan 2025 09:01 GMT, 9 min28 Jan 2025 09:10 GMT, 2.1 h28 Jan 2025 11:18 GMT, 20 min28 Jan 2025 11:38 GMT, 15 min28 Jan 2025 11:56 GMT, 3 min28 Jan 2025 12:00 GMT, 53 min28 Jan 2025 12:54 GMT, 9 min28 Jan 2025 13:04 GMT, 7 min28 Jan 2025 13:12 GMT, 18 min28 Jan 2025 13:36 GMT, 17 min28 Jan 2025 13:54 GMT, 3 min28 Jan 2025 13:58 GMT, 6 min28 Jan 2025 14:14 GMT, 17 min28 Jan 2025 15:36 GMT, 9 min28 Jan 2025 15:46 GMT, 2 min28 Jan 2025 15:50 GMT, 20 min28 Jan 2025 16:14 GMT, 7 min28 Jan 2025 16:31 GMT, 8 min28 Jan 2025 16:40 GMT, 46 min28 Jan 2025 17:31 GMT, 24 min28 Jan 2025 17:58 GMT, 23 min28 Jan 2025 18:23 GMT, 11 min28 Jan 2025 18:40 GMT, 62 min28 Jan 2025 19:42 GMT, 7 min28 Jan 2025 19:50 GMT, 75 min28 Jan 2025 21:07 GMT, 5 min28 Jan 2025 21:15 GMT, 36 min28 Jan 2025 21:52 GMT, 14 min28 Jan 2025 22:39 GMT, 7 min28 Jan 2025 22:49 GMT, 6 min29 Jan 2025 07:50 GMT, 24 min29 Jan 2025 08:16 GMT, 6 min29 Jan 2025 08:24 GMT, 14 min31 Jan 2025 03:48 GMT, 68 min31 Jan 2025 07:52 GMT, 10 min31 Jan 2025 08:23 GMT, 14 min15 Feb 2025 20:45 GMT, 2 min16 Feb 2025 10:06 GMT, 5 min16 Feb 2025 10:12 GMT, 8 min16 Feb 2025 10:24 GMT, 14 min24 Feb 2025 10:06 GMT, 5 min24 Feb 2025 11:00 GMT, 21 min22 Mar 2025 19:08 GMT, 39 min22 Mar 2025 19:50 GMT, 7 min23 Apr 2025 04:34 GMT, 2.7 h23 Apr 2025 07:18 GMT, 20 min27 May 2025 21:06 GMT, 52 min6 Jul 2025 08:34 GMT, 103 min6 Jul 2025 11:04 GMT, 2.4 h6 Jul 2025 13:48 GMT, 36 min7 Jul 2025 04:40 GMT, 35 min7 Jul 2025 06:32 GMT, 45 min21 Jul 2025 14:46 GMT, 5.8 h14 Sep 2025 16:32 GMT, 4.2 h23 Oct 2025 10:09 GMT, 29 min10 Nov 2025 07:55 GMT, 85 min10 Nov 2025 11:22 GMT, 10 h12 Nov 2025 00:42 GMT, 109 min12 Nov 2025 07:04 GMT, 15.9 h14 Nov 2025 07:16 GMT, 38.2 h22 Nov 2025 11:14 GMT, 17.2 h23 Nov 2025 05:12 GMT, 18 h24 Nov 2025 07:42 GMT, 84 min29 Nov 2025 10:10 GMT, 4 h4 Dec 2025 12:40 GMT, 12.1 h5 Dec 2025 07:10 GMT, 3.6 h5 Dec 2025 17:01 GMT, 11.1 h6 Dec 2025 06:46 GMT, 11.7 h6 Dec 2025 18:26 GMT, 60 min7 Dec 2025 14:20 GMT, 2 h7 Dec 2025 17:02 GMT, 9 min7 Dec 2025 18:46 GMT, 94 min9 Dec 2025 06:04 GMT, 17.8 h10 Dec 2025 07:20 GMT, 2.1 h16 Dec 2025 01:59 GMT, 24.9 h17 Dec 2025 06:35 GMT, 4.8 h17 Dec 2025 18:18 GMT, 2.1 h18 Dec 2025 00:13 GMT, 42 min18 Dec 2025 07:50 GMT, 23 min18 Dec 2025 12:46 GMT, 33 h19 Dec 2025 22:09 GMT, 13 min19 Dec 2025 22:33 GMT, 15 min20 Dec 2025 11:41 GMT, 26 min21 Dec 2025 23:37 GMT, 68 min22 Dec 2025 08:43 GMT, 2.4 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

010k20k30kJan 2025: 85 h spilling ≈ 7,383 m³ (range 2,941–18,534 m³)JanFeb 2025: 0.9 h spilling ≈ 78 m³ (range 31–196 m³)FebMar 2025: 0.8 h spilling ≈ 69 m³ (range 28–174 m³)MarApr 2025: 3.0 h spilling ≈ 260 m³ (range 104–653 m³)AprMay 2025: 0.9 h spilling ≈ 78 m³ (range 31–196 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 12 h spilling ≈ 1,032 m³ (range 411–2,592 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 4.2 h spilling ≈ 364 m³ (range 145–915 m³)SepOct 2025: 0.5 h spilling ≈ 43 m³ (range 17–109 m³)OctNov 2025: 108 h spilling ≈ 9,361 m³ (range 3,728–23,500 m³)NovDec 2025: 133 h spilling ≈ 11,564 m³ (range 4,606–29,032 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 07:16Fleckney Sewage Treatment Works1.6 days1,320 – 8,320 m³
18 Dec 2025, 12:46Fleckney Sewage Treatment Works1.4 days1,139 – 7,180 m³
5 Jan 2025, 17:56Fleckney Sewage Treatment Works1.4 days1,130 – 7,122 m³
16 Dec 2025, 01:59Fleckney Sewage Treatment Works1.0 days860 – 5,423 m³
23 Nov 2025, 05:12Fleckney Sewage Treatment Works18.0 h620 – 3,909 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate30,224 m³range 12,039 – 75,879 m³
In litres30.2 millionrange 12.0 million – 75.9 million L
Olympic swimming pools12at 2,500 m³ each
Organic load, as people's raw sewage45,336person-days of untreated BOD

Assumed spill rate while spilling: 9.6 – 60.5 L/s (central 24.1 L/s), from a dry-weather flow of 9.6 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 482 kg2,720 kg15,176 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,264 kg12,845 kg54,709 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 23 kg190 kg706 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 14 kg79 kg410 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.2 trillion organisms30.2 trillion organisms758.8 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Fleckney Sewage Treatment Works

Storm tank at sewage works · discharges to Tributary of Burton Brook

Spills 2025
43 (348 hours) · down 46% on 2024
Spills 2024
79 (787 hours)
Long-term average
53.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing, Operational investigation completed
Improvement
UWWTR improvement ongoing, Operational improvement completed
WFD catchment
Sence from Burton Brook to Countesthorpe Brook (GB104028046620)
Outlet location
SP6565994523 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00909 · T/51/45576/R · company name: FLECKNEY STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.