Storm overflow register · Severn Trent Water

Gloucester Netheridge sewage works: storm overflow spills 2025

Gloucester Netheridge sewage treatment works, run by Severn Trent Water, has 2 monitored storm overflows discharging to River Severn. In 2025 they recorded 65 spills totalling 422 hours, against 139 spills and 1,004 hours in 2024. By hours spilling, it ranks 100 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 191,433 population equivalent (GLOUCESTER NetheridgeSTW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecGloucester Netheridge…3 spills, 4.1 h, 1 Jan to 1 Jan41 spills, 57.2 h, 5 Jan to 9 Jan5 spills, 5.2 h, 24 Jan to 24 Jan43 spills, 72.9 h, 26 Jan to 2 Feb22 Feb 2025 15:22 GMT, 48 min14 spills, 27.2 h, 23 Feb to 25 Feb3 spills, 1.1 h, 26 Feb to 26 Feb23 Apr 2025 02:34 GMT, 63 min7 Jun 2025 17:42 GMT, 77 min12 Jun 2025 13:45 GMT, 54 min31 Jul 2025 17:00 GMT, 60 min3 spills, 3.6 h, 3 Sep to 4 Sep7 Sep 2025 11:52 GMT, 74 min4 spills, 2.9 h, 14 Sep to 14 Sep19 Oct 2025 19:58 GMT, 74 min2 spills, 0.1 h, 23 Oct to 23 Oct3 spills, 3.3 h, 29 Oct to 29 Oct4 Nov 2025 21:36 GMT, 10 min3 spills, 3.2 h, 10 Nov to 10 Nov9 spills, 14.4 h, 11 Nov to 12 Nov19 spills, 40.2 h, 13 Nov to 16 Nov3 spills, 1.5 h, 29 Nov to 29 Nov8 spills, 8 h, 1 Dec to 2 Dec47 spills, 54 h, 5 Dec to 10 Dec55 spills, 85.7 h, 15 Dec to 21 DecGloucester Netheridge…5 spills, 12.4 h, 5 Jan to 6 Jan5 spills, 4.7 h, 26 Jan to 27 Jan12 Nov 2025 06:21 GMT, 38 min14 Nov 2025 09:42 GMT, 9.2 h15 Dec 2025 21:50 GMT, 12 min18 Dec 2025 13:17 GMT, 2.8 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0500k1M1.5MJan 2025: 155 h spilling ≈ 507,103 m³ (range 201,990-1.3 million m³)JanFeb 2025: 31 h spilling ≈ 101,355 m³ (range 40,372-254,456 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 1.1 h spilling ≈ 3,608 m³ (range 1,437-9,058 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 2.2 h spilling ≈ 7,216 m³ (range 2,874-18,117 m³)JunJul 2025: 1.0 h spilling ≈ 3,280 m³ (range 1,307-8,235 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 7.7 h spilling ≈ 25,257 m³ (range 10,060-63,408 m³)SepOct 2025: 4.7 h spilling ≈ 15,416 m³ (range 6,141-38,704 m³)OctNov 2025: 69 h spilling ≈ 227,639 m³ (range 90,673-571,496 m³)NovDec 2025: 151 h spilling ≈ 494,310 m³ (range 196,894-1.2 million m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
15 Dec 2025, 09:54Gloucester Netheridge STW1.3 days39,588 - 249,515 m³
5 Jan 2025, 21:36Gloucester Netheridge STW1.1 days34,906 - 220,007 m³
14 Nov 2025, 05:48Gloucester Netheridge STW1.1 days33,948 - 213,968 m³
18 Dec 2025, 12:34Gloucester Netheridge STW17.0 h22,211 - 139,992 m³
23 Feb 2025, 14:50Gloucester Netheridge STW16.8 h21,971 - 138,482 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate1.4 million m³range 551,748 - 3.5 million m³
In litres1.4 billionrange 551.7 million - 3.5 billion L
Olympic swimming pools554at 2,500 m³ each
Organic load, as people's raw sewage2.1 millionperson-days of untreated BOD

Assumed spill rate while spilling: 362.9 - 2,287.4 L/s (central 911.1 L/s), from a dry-weather flow of 362.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 22,070 kg124,667 kg695,512 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 57,934 kg588,703 kg2.5 million kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 1,048 kg8,727 kg32,341 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 662 kg3,601 kg18,779 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 55.2 trillion organisms1.4 × 10¹⁵ organisms3.5 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Gloucester Netheridge STW

Storm tank at sewage works · discharges to River Severn

Spills 2025
57 (392 hours) · down 47% on 2024
Spills 2024
107 (888 hours)
Long-term average
85.7 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Performance - SW Infiltration
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
SEVERN UPPER (GB530905415403)
Outlet location
SO8079016067 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00966 · S/20/26440/R · company name: NETHERIDGE STW (SSTO)

Gloucester Netheridge STW

Inlet overflow at sewage works · discharges to River Severn

Spills 2025
8 (30 hours) · down 75% on 2024
Spills 2024
32 (116 hours)
Long-term average
52.0 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
SEVERN UPPER (GB530905415403)
Outlet location
SO8079016067 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00965 · S/20/26440/R · company name: NETHERIDGE STW (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.