Storm overflow register · Severn Trent Water

Harworth sewage works: storm overflow spills 2025

Harworth sewage treatment works, run by Severn Trent Water, has 2 monitored storm overflows discharging to Harworth Sewage Dyke. In 2025 they recorded 30 spills totalling 99 hours, against 34 spills and 179 hours in 2024. By hours spilling, it ranks 259 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 8,594 population equivalent (HARWORTH STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecHarworth Sewage…5 Jan 2025 17:16 GMT, 31.6 h7 Jan 2025 01:25 GMT, 17 min27 Jan 2025 05:52 GMT, 105 min27 Jan 2025 21:39 GMT, 101 min20 Sep 2025 21:30 GMT, 5.3 h12 Nov 2025 17:46 GMT, 23 min14 Nov 2025 11:19 GMT, 18.6 h15 Nov 2025 06:20 GMT, 108 min15 Nov 2025 08:18 GMT, 5.6 h15 Nov 2025 19:08 GMT, 17 min18 Dec 2025 18:01 GMT, 3.9 hHarworth Sewage…5 Jan 2025 20:23 GMT, 1 min5 Jan 2025 20:33 GMT, 1 min5 Jan 2025 20:45 GMT, 1 min5 Jan 2025 21:35 GMT, 1 min5 Jan 2025 22:15 GMT, 1 min5 Jan 2025 22:21 GMT, 1 min5 Jan 2025 22:31 GMT, 1 min5 Jan 2025 22:45 GMT, 1 min5 Jan 2025 23:15 GMT, 3 min5 Jan 2025 23:35 GMT, 1 min6 Jan 2025 03:51 GMT, 1 min6 Jan 2025 04:03 GMT, 3 min6 Jan 2025 05:07 GMT, 1 min6 Jan 2025 05:27 GMT, 1 min24 May 2025 01:56 GMT, 21 min24 May 2025 02:56 GMT, 6 min6 Jul 2025 07:09 GMT, 46 min19 Jul 2025 12:32 GMT, 64 min20 Jul 2025 12:44 GMT, 3 min10 Sep 2025 20:03 GMT, 16 min20 Sep 2025 16:24 GMT, 7 min20 Sep 2025 17:23 GMT, 19 min20 Sep 2025 20:04 GMT, 2.9 h21 Sep 2025 00:34 GMT, 29 min19 Oct 2025 21:45 GMT, 29 min23 Oct 2025 00:00 GMT, 33 min4 Nov 2025 19:31 GMT, 29 min10 Nov 2025 16:09 GMT, 60 min12 Nov 2025 18:03 GMT, 46 min14 Nov 2025 08:01 GMT, 109 min14 Nov 2025 11:47 GMT, 2.2 h14 Nov 2025 15:25 GMT, 25 min14 Nov 2025 16:10 GMT, 5.3 h14 Nov 2025 22:36 GMT, 2.2 h29 Nov 2025 21:00 GMT, 49 min4 Dec 2025 16:56 GMT, 39 min5 Dec 2025 19:12 GMT, 23 min9 Dec 2025 05:56 GMT, 7 min12 Dec 2025 12:12 GMT, 13 min15 Dec 2025 19:25 GMT, 10 min18 Dec 2025 14:09 GMT, 32 min18 Dec 2025 15:04 GMT, 2.4 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

05,00010k15k20kJan 2025: 36 h spilling ≈ 5,242 m³ (range 2,088–13,161 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.4 h spilling ≈ 59 m³ (range 23–148 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 1.9 h spilling ≈ 280 m³ (range 111–702 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 9.4 h spilling ≈ 1,384 m³ (range 551–3,475 m³)SepOct 2025: 1.0 h spilling ≈ 147 m³ (range 59–370 m³)OctNov 2025: 42 h spilling ≈ 6,126 m³ (range 2,440–15,379 m³)NovDec 2025: 8.4 h spilling ≈ 1,237 m³ (range 493–3,105 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 17:16Harworth Sewage Treatment Works1.3 days1,854 – 11,688 m³
14 Nov 2025, 11:19Harworth Sewage Treatment Works18.6 h1,089 – 6,864 m³
15 Nov 2025, 08:18Harworth Sewage Treatment Works5.6 h328 – 2,070 m³
20 Sep 2025, 21:30Harworth Sewage Treatment Works5.3 h312 – 1,965 m³
14 Nov 2025, 16:10Harworth Sewage Treatment Works5.3 h310 – 1,953 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate14,504 m³range 5,777 – 36,414 m³
In litres14.5 millionrange 5.8 million – 36.4 million L
Olympic swimming pools5.8at 2,500 m³ each
Organic load, as people's raw sewage21,757person-days of untreated BOD

Assumed spill rate while spilling: 16.3 – 102.7 L/s (central 40.9 L/s), from a dry-weather flow of 16.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 231 kg1,305 kg7,283 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 607 kg6,164 kg26,254 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 11 kg91 kg339 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 6.9 kg38 kg197 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 577.7 billion organisms14.5 trillion organisms364.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Harworth Sewage Treatment Works

Storm tank at sewage works · discharges to Harworth Sewage Dyke

Spills 2025
9 (71 hours) · down 64% on 2024
Spills 2024
25 (177 hours)
Long-term average
30.2 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Torne from Ruddle to St Catherine's Well Stream (GB104028058400)
Outlet location
SK6111692053 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01079 · T/83/45790/R · company name: HARWORTH STW (SSTO)

Harworth Sewage Treatment Works

Inlet overflow at sewage works · discharges to Harworth Sewage Dyke

Spills 2025
21 (27 hours) · up 133% on 2024
Spills 2024
9 (1.7 hours)
Long-term average
15.6 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation ongoing, Operational investigation ongoing
Improvement
No improvement action in reporting period
WFD catchment
Torne from Ruddle to St Catherine's Well Stream (GB104028058400)
Outlet location
SK6111692053 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01078 · T/83/45790/R · company name: HARWORTH STW (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.