Storm overflow register · Severn Trent Water

Itchen Bank sewage works: storm overflow spills 2025

Itchen Bank sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to River Itchen. In 2025 it recorded 53 spills totalling 561 hours, against 121 spills and 1,834 hours in 2024. By hours spilling, it ranks 73 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 15,594 population equivalent (SOUTHAM DISTRICT STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecItchen Bank Sewage…1 Jan 2025 11:17 GMT, 2.7 h1 Jan 2025 14:02 GMT, 50 min1 Jan 2025 16:38 GMT, 15 min5 Jan 2025 10:10 GMT, 11.4 h5 Jan 2025 21:55 GMT, 41.2 h7 Jan 2025 15:25 GMT, 115 min7 Jan 2025 17:55 GMT, 7.3 h8 Jan 2025 01:40 GMT, 4.4 h8 Jan 2025 06:25 GMT, 3.7 h8 Jan 2025 10:25 GMT, 2.6 h8 Jan 2025 13:55 GMT, 2.9 h8 Jan 2025 17:10 GMT, 10 min8 Jan 2025 17:55 GMT, 55 min8 Jan 2025 19:10 GMT, 3.2 h9 Jan 2025 11:01 GMT, 29 min9 Jan 2025 12:10 GMT, 19 min9 Jan 2025 12:32 GMT, 35 min9 Jan 2025 16:25 GMT, 16 min9 Jan 2025 17:32 GMT, 55 min9 Jan 2025 18:31 GMT, 56 min9 Jan 2025 19:31 GMT, 63 min19 Jan 2025 21:37 GMT, 18 min19 Jan 2025 22:47 GMT, 24 min20 Jan 2025 10:50 GMT, 22 min26 Jan 2025 16:47 GMT, 3.6 h26 Jan 2025 20:40 GMT, 20 min26 Jan 2025 22:03 GMT, 84 min26 Jan 2025 23:33 GMT, 21.3 h27 Jan 2025 21:10 GMT, 2.2 h28 Jan 2025 01:33 GMT, 39 min28 Jan 2025 03:19 GMT, 24 min28 Jan 2025 07:05 GMT, 17.3 h29 Jan 2025 01:10 GMT, 10 min29 Jan 2025 01:45 GMT, 3.2 h29 Jan 2025 08:19 GMT, 6.6 h29 Jan 2025 16:20 GMT, 30 min29 Jan 2025 17:35 GMT, 30 min29 Jan 2025 18:25 GMT, 16 min29 Jan 2025 18:46 GMT, 43 min29 Jan 2025 19:31 GMT, 2.1 h29 Jan 2025 22:04 GMT, 24 min31 Jan 2025 07:49 GMT, 3.4 h31 Jan 2025 11:16 GMT, 19 min31 Jan 2025 12:15 GMT, 102 min31 Jan 2025 14:02 GMT, 52 min31 Jan 2025 15:40 GMT, 10 min31 Jan 2025 16:21 GMT, 48 min31 Jan 2025 17:17 GMT, 25 min31 Jan 2025 18:10 GMT, 40 min31 Jan 2025 19:10 GMT, 34 min31 Jan 2025 19:48 GMT, 80 min1 Feb 2025 12:10 GMT, 32 min1 Feb 2025 13:49 GMT, 24 min1 Feb 2025 18:45 GMT, 25 min1 Feb 2025 19:21 GMT, 16 min1 Feb 2025 21:06 GMT, 17 min15 Feb 2025 10:51 GMT, 5.9 h15 Feb 2025 18:01 GMT, 48 min15 Feb 2025 20:33 GMT, 4.2 h16 Feb 2025 13:19 GMT, 8.6 h16 Feb 2025 22:05 GMT, 32 min23 Feb 2025 22:21 GMT, 4.1 h24 Feb 2025 02:31 GMT, 11.4 h24 Feb 2025 14:03 GMT, 67 min24 Feb 2025 15:21 GMT, 32 min24 Feb 2025 16:03 GMT, 39 min24 Feb 2025 16:47 GMT, 57 min24 Feb 2025 17:47 GMT, 2.3 h24 Feb 2025 20:25 GMT, 34 min24 Feb 2025 21:55 GMT, 25 min24 Feb 2025 22:55 GMT, 10 min24 Feb 2025 23:37 GMT, 17 min25 Feb 2025 13:22 GMT, 16 min25 Feb 2025 16:40 GMT, 14 min25 Feb 2025 17:15 GMT, 28 min25 Feb 2025 18:25 GMT, 115 min25 Feb 2025 20:40 GMT, 64 min25 Feb 2025 22:17 GMT, 24 min26 Feb 2025 09:31 GMT, 3.9 h26 Feb 2025 13:38 GMT, 11 min26 Feb 2025 14:33 GMT, 3.1 h26 Feb 2025 18:02 GMT, 4.2 h26 Feb 2025 22:32 GMT, 18 min26 Feb 2025 23:10 GMT, 25 min27 Feb 2025 00:05 GMT, 18 min27 Feb 2025 09:06 GMT, 94 min27 Feb 2025 11:53 GMT, 12 min27 Feb 2025 13:23 GMT, 13 min27 Feb 2025 18:05 GMT, 15 min27 Feb 2025 18:40 GMT, 63 min27 Feb 2025 19:50 GMT, 21 min27 Feb 2025 21:06 GMT, 15 min27 Feb 2025 21:35 GMT, 50 min27 Feb 2025 22:50 GMT, 19 min22 Mar 2025 21:30 GMT, 26 h23 Mar 2025 23:35 GMT, 20 min24 Mar 2025 08:53 GMT, 107 min24 Mar 2025 12:06 GMT, 58 min24 Mar 2025 19:25 GMT, 55 min24 Mar 2025 20:40 GMT, 18 min23 Apr 2025 02:44 GMT, 5.6 h23 Apr 2025 08:48 GMT, 7 min23 Apr 2025 09:52 GMT, 31 min23 Apr 2025 13:27 GMT, 13 min27 May 2025 12:52 GMT, 2.4 h27 May 2025 15:16 GMT, 16 min5 Jun 2025 19:38 GMT, 2 h5 Jun 2025 21:47 GMT, 8 min7 Jun 2025 19:21 GMT, 37 min19 Jul 2025 10:22 GMT, 2.6 h19 Jul 2025 13:04 GMT, 9 min19 Jul 2025 13:18 GMT, 8 min14 Sep 2025 16:40 GMT, 5.8 h12 Nov 2025 07:17 GMT, 4.9 h12 Nov 2025 12:20 GMT, 9.7 h14 Nov 2025 08:48 GMT, 39.8 h16 Nov 2025 11:50 GMT, 13.8 h22 Nov 2025 18:01 GMT, 5.9 h23 Nov 2025 06:49 GMT, 14.8 h1 Dec 2025 11:34 GMT, 94 min1 Dec 2025 13:35 GMT, 12.6 h2 Dec 2025 10:04 GMT, 36 min2 Dec 2025 18:34 GMT, 3.3 h4 Dec 2025 14:07 GMT, 31 min4 Dec 2025 16:10 GMT, 13 min4 Dec 2025 17:25 GMT, 4.4 h4 Dec 2025 22:10 GMT, 9 min5 Dec 2025 19:47 GMT, 28.9 h7 Dec 2025 13:16 GMT, 9.7 h9 Dec 2025 07:03 GMT, 6.1 h9 Dec 2025 13:19 GMT, 10.5 h10 Dec 2025 10:04 GMT, 62 min15 Dec 2025 23:16 GMT, 51.8 h18 Dec 2025 03:40 GMT, 10 min18 Dec 2025 06:55 GMT, 62.7 h20 Dec 2025 22:09 GMT, 10 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

050k100k150kJan 2025: 161 h spilling ≈ 42,938 m³ (range 17,103–107,798 m³)JanFeb 2025: 66 h spilling ≈ 17,688 m³ (range 7,046–44,407 m³)FebMar 2025: 30 h spilling ≈ 8,069 m³ (range 3,214–20,258 m³)MarApr 2025: 6.5 h spilling ≈ 1,737 m³ (range 692–4,360 m³)AprMay 2025: 2.6 h spilling ≈ 695 m³ (range 277–1,744 m³)MayJun 2025: 2.8 h spilling ≈ 748 m³ (range 298–1,878 m³)JunJul 2025: 2.9 h spilling ≈ 775 m³ (range 309–1,945 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 5.8 h spilling ≈ 1,550 m³ (range 617–3,891 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 89 h spilling ≈ 23,727 m³ (range 9,451–59,567 m³)NovDec 2025: 194 h spilling ≈ 51,943 m³ (range 20,690–130,404 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
18 Dec 2025, 06:55Itchen Bank Sewage Treatment Works2.6 days6,677 – 42,082 m³
15 Dec 2025, 23:16Itchen Bank Sewage Treatment Works2.2 days5,515 – 34,759 m³
5 Jan 2025, 21:55Itchen Bank Sewage Treatment Works1.7 days4,381 – 27,615 m³
14 Nov 2025, 08:48Itchen Bank Sewage Treatment Works1.7 days4,234 – 26,687 m³
5 Dec 2025, 19:47Itchen Bank Sewage Treatment Works1.2 days3,074 – 19,375 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate149,843 m³range 59,685 – 376,186 m³
In litres149.8 millionrange 59.7 million – 376.2 million L
Olympic swimming pools60at 2,500 m³ each
Organic load, as people's raw sewage224,764person-days of untreated BOD

Assumed spill rate while spilling: 29.6 – 186.3 L/s (central 74.2 L/s), from a dry-weather flow of 29.6 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 2,387 kg13,486 kg75,237 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 6,267 kg63,683 kg271,230 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 113 kg944 kg3,499 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 72 kg390 kg2,031 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 6.0 trillion organisms149.8 trillion organisms3.8 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Itchen Bank Sewage Treatment Works

Storm tank at sewage works · discharges to River Itchen

Spills 2025
53 (561 hours) · down 56% on 2024
Spills 2024
121 (1,834 hours)
Long-term average
74.8 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
UWWTR improvement completed, Operational improvement completed
WFD catchment
Itchen - conf R Stowe to conf R Leam (GB109054044110)
Outlet location
SP4067462821 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01223 · S/12/26557/R · company name: ITCHEN BANK STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.