Storm overflow register · Severn Trent Water

Kineton sewage works: storm overflow spills 2025

Kineton sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to River Dene. In 2025 it recorded 19 spills totalling 194 hours, against 89 spills and 1,037 hours in 2024. By hours spilling, it ranks 180 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 2,245 population equivalent (KINETON STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecKineton Sewage…5 Jan 2025 18:25 GMT, 22.8 h6 Jan 2025 17:15 GMT, 16.4 h7 Jan 2025 09:50 GMT, 62 min7 Jan 2025 11:20 GMT, 106 min7 Jan 2025 13:23 GMT, 21 min7 Jan 2025 13:45 GMT, 88 min7 Jan 2025 16:34 GMT, 17 min7 Jan 2025 17:11 GMT, 74 min7 Jan 2025 18:48 GMT, 25 min7 Jan 2025 20:55 GMT, 73 min7 Jan 2025 22:37 GMT, 71 min27 Jan 2025 02:00 GMT, 16.4 h28 Jan 2025 13:24 GMT, 13.5 h21 Jul 2025 20:21 GMT, 2.3 h10 Nov 2025 12:10 GMT, 39 min11 Nov 2025 23:50 GMT, 4.6 h12 Nov 2025 08:02 GMT, 3.5 h14 Nov 2025 09:22 GMT, 13 min14 Nov 2025 09:53 GMT, 29.7 h5 Dec 2025 23:55 GMT, 70 min6 Dec 2025 05:40 GMT, 14.2 h16 Dec 2025 05:55 GMT, 23.5 h18 Dec 2025 14:01 GMT, 36.1 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

02,0004,0006,0008,000Jan 2025: 78 h spilling ≈ 3,000 m³ (range 1,195–7,533 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 2.2 h spilling ≈ 85 m³ (range 34–212 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 39 h spilling ≈ 1,489 m³ (range 593–3,737 m³)NovDec 2025: 75 h spilling ≈ 2,881 m³ (range 1,148–7,233 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
18 Dec 2025, 14:01Kineton Sewage Treatment Works1.5 days553 – 3,486 m³
14 Nov 2025, 09:53Kineton Sewage Treatment Works1.2 days456 – 2,871 m³
16 Dec 2025, 05:55Kineton Sewage Treatment Works23.5 h360 – 2,269 m³
5 Jan 2025, 18:25Kineton Sewage Treatment Works22.8 h349 – 2,199 m³
27 Jan 2025, 02:00Kineton Sewage Treatment Works16.4 h252 – 1,585 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate7,459 m³range 2,971 – 18,725 m³
In litres7.5 millionrange 3.0 million – 18.7 million L
Olympic swimming pools3.0at 2,500 m³ each
Organic load, as people's raw sewage11,188person-days of untreated BOD

Assumed spill rate while spilling: 4.3 – 26.8 L/s (central 10.7 L/s), from a dry-weather flow of 4.3 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 119 kg671 kg3,745 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 312 kg3,170 kg13,501 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 5.6 kg47 kg174 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 3.6 kg19 kg101 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 297.1 billion organisms7.5 trillion organisms187.3 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Kineton Sewage Treatment Works

Inlet overflow at sewage works (with treatment) · discharges to River Dene

Spills 2025
19 (194 hours) · down 79% on 2024
Spills 2024
89 (1,037 hours)
Long-term average
48.8 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement completed
Treatment
Reed bed
WFD catchment
Dene - source to Butlers Marston (GB109054039501)
Outlet location
SP3257050702 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01266 · S/13/25745/R · company name: KINETON (STW)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.