Storm overflow register · Severn Trent Water
Lichfield sewage works: storm overflow spills 2025
Lichfield sewage treatment works, run by Severn Trent Water, has 2 monitored storm overflows discharging to Full Brook. In 2025 they recorded 23 spills totalling 117 hours, against 55 spills and 290 hours in 2024. By hours spilling, it ranks 241 of 435 Severn Trent Water works, where 1 spilled longest.
Works size: 38,555 population equivalent (LICHFIELD STW, UWWTD 2018). Used for the spill volume estimate.
Every spill in 2025
Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.
Estimated spill volume by month, 2025
Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.
Longest single spills
| Started (GMT) | Overflow | Duration | Estimated volume |
|---|---|---|---|
| 14 Nov 2025, 07:53 | Lichfield Sewage Treatment Works | 1.3 days | 8,438 – 53,183 m³ |
| 5 Jan 2025, 18:06 | Lichfield Sewage Treatment Works | 1.2 days | 7,425 – 46,798 m³ |
| 18 Dec 2025, 15:36 | Lichfield Sewage Treatment Works | 9.5 h | 2,509 – 15,811 m³ |
| 29 Nov 2025, 07:54 | Lichfield Sewage Treatment Works | 7.6 h | 2,000 – 12,605 m³ |
| 19 Oct 2025, 19:45 | Lichfield Sewage Treatment Works | 3.5 h | 908 – 5,722 m³ |
Estimated 2025 spill volume and pollution
Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.
Assumed spill rate while spilling: 73.1 – 460.7 L/s (central 183.5 L/s), from a dry-weather flow of 73.1 L/s.
| Pollutant released | Low | Central | High | Concentration used (low / typical / high) |
|---|---|---|---|---|
| BOD₅ (organic load) | 1,235 kg | 6,974 kg | 38,909 kg | 40 / 90 / 200 mg/L Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi) |
| Suspended solids | 3,241 kg | 32,933 kg | 140,265 kg | 105 / 425 / 721 mg/L Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi) |
| Ammonium-N | 59 kg | 488 kg | 1,809 kg | 1.9 / 6.3 / 9.3 mg/L Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found |
| Total phosphorus | 37 kg | 201 kg | 1,051 kg | 1.2 / 2.6 / 5.4 mg/L Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier |
| E. coli | 3.1 trillion organisms | 77.5 trillion organisms | 1.9 × 10¹⁵ organisms | 10,000 / 100,000 / 1.0 million per 100 mL Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint |
Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.
Lichfield Sewage Treatment Works
Inlet overflow at sewage works · discharges to Full Brook
- Spills 2025
- 13 (91 hours) · down 61% on 2024
- Spills 2024
- 33 (219 hours)
- Long-term average
- 44.6 spills a year (monitored since 2021)
- Monitor uptime
- 100% of the year
- Investigation
- UWWTR investigation completed, Operational investigation completed
- Improvement
- Operational improvement completed
- WFD catchment
- Pyford Brook Catchment (trib of Trent) (GB104028047250)
- Outlet location
- SK1270712894 (OS grid reference) · View on Apple Maps
- EA ID / permit
- SVT01358 · T/07/36033/R · company name: LICHFIELD STW (CSO)
Lichfield Sewage Treatment Works
Storm tank at sewage works · discharges to Full Brook
- Spills 2025
- 10 (26 hours) · down 55% on 2024
- Spills 2024
- 22 (71 hours)
- Long-term average
- 16.0 spills a year (monitored since 2020)
- Monitor uptime
- 100% of the year
- Investigation
- UWWTR investigation ongoing, Operational investigation completed
- Improvement
- Operational improvement completed
- WFD catchment
- Pyford Brook Catchment (trib of Trent) (GB104028047250)
- Outlet location
- SK1270712894 (OS grid reference) · View on Apple Maps
- EA ID / permit
- SVT01359 · T/07/36033/R · company name: LICHFILED STW (SSTO)
How the estimate works
- Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
- Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
- Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
- High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
- Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
- Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].
What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.
Sources
- EA: Water companies – environmental permits for storm overflows and emergency overflows
- EA: Water resources 2024 to 2025 – per capita consumption
- HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
- Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
- Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
- US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
- Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
- Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth
← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.