Storm overflow register · Severn Trent Water

Long Whatton sewage works: storm overflow spills 2025

Long Whatton sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Long Whatton Brook. In 2025 it recorded 55 spills totalling 626 hours, against 74 spills and 602 hours in 2024. By hours spilling, it ranks 59 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 2,533 population equivalent (LONG WHATTON STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecLong Whatton STW20 spills, 25.7 h, 1 Jan to 2 Jan26 spills, 120.1 h, 5 Jan to 11 Jan6 spills, 2.4 h, 12 Jan to 12 Jan39 spills, 96.4 h, 27 Jan to 1 Feb2 spills, 0.8 h, 2 Feb to 2 Feb4 spills, 1.6 h, 27 May to 27 May3 spills, 2.5 h, 6 Jun to 6 Jun14 Sep 2025 17:22 GMT, 5.2 h2 spills, 4.4 h, 17 Sep to 17 Sep2 spills, 3.5 h, 3 Oct to 3 Oct4 Nov 2025 20:46 GMT, 2.7 h14 spills, 14.4 h, 10 Nov to 10 Nov2 spills, 8.4 h, 12 Nov to 12 Nov14 Nov 2025 07:18 GMT, 62.3 h4 spills, 18.7 h, 22 Nov to 23 Nov29 Nov 2025 09:14 GMT, 15.4 h11 spills, 30.8 h, 1 Dec to 2 Dec4 Dec 2025 19:32 GMT, 2.5 h2 spills, 35 h, 5 Dec to 7 Dec9 spills, 37.7 h, 9 Dec to 10 Dec5 spills, 108.2 h, 16 Dec to 20 Dec3 spills, 27.3 h, 21 Dec to 22 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

010k20k30kJan 2025: 238 h spilling ≈ 10,312 m³ (range 4,108-25,889 m³)JanFeb 2025: 7.8 h spilling ≈ 339 m³ (range 135-850 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AprMay 2025: 1.6 h spilling ≈ 69 m³ (range 28-174 m³)MayJun 2025: 2.5 h spilling ≈ 109 m³ (range 43-272 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 9.6 h spilling ≈ 417 m³ (range 166-1,046 m³)SepOct 2025: 3.5 h spilling ≈ 152 m³ (range 61-381 m³)OctNov 2025: 122 h spilling ≈ 5,291 m³ (range 2,107-13,282 m³)NovDec 2025: 242 h spilling ≈ 10,481 m³ (range 4,175-26,314 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 06:32Long Whatton STW3.8 days1,575 - 9,926 m³
18 Dec 2025, 04:59Long Whatton STW2.7 days1,114 - 7,021 m³
14 Nov 2025, 07:18Long Whatton STW2.6 days1,078 - 6,792 m³
27 Jan 2025, 01:34Long Whatton STW2.1 days879 - 5,541 m³
5 Dec 2025, 18:24Long Whatton STW1.2 days478 - 3,015 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate27,174 m³range 10,824 - 68,221 m³
In litres27.2 millionrange 10.8 million - 68.2 million L
Olympic swimming pools11at 2,500 m³ each
Organic load, as people's raw sewage40,761person-days of untreated BOD

Assumed spill rate while spilling: 4.8 - 30.3 L/s (central 12.1 L/s), from a dry-weather flow of 4.8 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 433 kg2,446 kg13,644 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 1,137 kg11,549 kg49,187 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 21 kg171 kg634 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 13 kg71 kg368 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 1.1 trillion organisms27.2 trillion organisms682.2 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Long Whatton STW

Storm tank at sewage works · discharges to Long Whatton Brook

Spills 2025
55 (626 hours) · down 26% on 2024
Spills 2024
74 (602 hours)
Long-term average
101.5 spills a year (monitored since 2020)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Long Whatton Brook Catchment (trib of Soar) (GB104028047170)
Outlet location
SK4918023330 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01407 · T/57/08423/R · company name: LONG WHATTON STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.