Storm overflow register · Severn Trent Water

Malvern sewage works: storm overflow spills 2025

Malvern sewage treatment works, run by Severn Trent Water, has 3 monitored storm overflows discharging to River Severn, Pool Brook. In 2025 they recorded 103 spills totalling 829 hours, against 231 spills and 2,623 hours in 2024. By hours spilling, it ranks 35 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 36,121 population equivalent (MALVERN STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecMalvern Sewage…1 Jan 2025 10:21 GMT, 6.1 h14 spills, 90.3 h, 5 Jan to 9 Jan24 Jan 2025 04:30 GMT, 7.5 h30 spills, 94.7 h, 26 Jan to 31 Jan2 spills, 10.5 h, 15 Feb to 15 Feb4 spills, 5.9 h, 21 Feb to 22 Feb30 spills, 54 h, 23 Feb to 27 Feb3 spills, 10.9 h, 23 Apr to 23 Apr7 Jun 2025 16:53 GMT, 3 h12 Jun 2025 13:40 GMT, 8.1 h7 Sep 2025 11:08 GMT, 3.3 h5 spills, 7.4 h, 14 Sep to 15 Sep3 spills, 2.3 h, 3 Oct to 3 Oct2 spills, 8.6 h, 19 Oct to 20 Oct23 Oct 2025 17:39 GMT, 14 min4 Nov 2025 21:02 GMT, 23 min2 spills, 21.6 h, 11 Nov to 13 Nov3 spills, 4.1 h, 14 Nov to 14 Nov14 spills, 33.3 h, 15 Nov to 17 Nov4 spills, 4.5 h, 22 Nov to 23 Nov3 spills, 3.4 h, 29 Nov to 29 Nov6 spills, 25.2 h, 1 Dec to 2 Dec6 spills, 4.3 h, 4 Dec to 4 Dec33 spills, 106.7 h, 5 Dec to 12 Dec42 spills, 121.2 h, 15 Dec to 22 DecMalvern Sewage…1 Jan 2025 08:37 GMT, 110 min3 spills, 35.7 h, 5 Jan to 7 Jan10 spills, 29 h, 26 Jan to 28 Jan15 Feb 2025 09:40 GMT, 113 min21 Feb 2025 19:13 GMT, 68 min6 spills, 15 h, 23 Feb to 24 Feb2 spills, 4.5 h, 23 Apr to 23 Apr3 Jun 2025 08:36 GMT, 20 min7 Jun 2025 14:58 GMT, 29 min2 spills, 0.4 h, 12 Jun to 12 Jun20 Jul 2025 11:55 GMT, 18 min31 Jul 2025 02:13 GMT, 10 min3 spills, 1.9 h, 7 Sep to 7 Sep8 Sep 2025 14:18 GMT, 14 min2 spills, 0.3 h, 12 Sep to 13 Sep2 spills, 0.6 h, 14 Sep to 14 Sep3 Oct 2025 14:28 GMT, 6 min2 spills, 2.4 h, 19 Oct to 19 Oct4 Nov 2025 18:07 GMT, 71 min12 Nov 2025 07:40 GMT, 3.3 h13 spills, 37.5 h, 14 Nov to 16 Nov1 Dec 2025 18:55 GMT, 4.5 h3 spills, 5.9 h, 6 Dec to 6 Dec2 spills, 4.8 h, 9 Dec to 9 Dec6 spills, 8.7 h, 18 Dec to 18 DecMalvern Sewage…1 Jan 2025 08:43 GMT, 4 min4 spills, 0.7 h, 26 Jan to 27 Jan21 Feb 2025 19:14 GMT, 1 min3 spills, 0.6 h, 23 Feb to 23 Feb12 Jun 2025 12:19 GMT, 77 min2 spills, 0.2 h, 20 Jul to 20 Jul2 spills, 0.4 h, 31 Jul to 31 Jul10 spills, 0.5 h, 7 Sep to 7 Sep8 Sep 2025 14:25 GMT, 4 min12 Nov 2025 08:08 GMT, 21 min8 spills, 24.5 h, 14 Nov to 15 Nov1 Dec 2025 18:13 GMT, 69 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

0200k400k600kJan 2025: 266 h spilling ≈ 164,507 m³ (range 65,527-413,001 m³)JanFeb 2025: 89 h spilling ≈ 55,021 m³ (range 21,916-138,133 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 15 h spilling ≈ 9,469 m³ (range 3,772-23,773 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MayJun 2025: 14 h spilling ≈ 8,417 m³ (range 3,353-21,132 m³)JunJul 2025: 1.1 h spilling ≈ 681 m³ (range 271-1,709 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 14 h spilling ≈ 8,912 m³ (range 3,550-22,375 m³)SepOct 2025: 14 h spilling ≈ 8,417 m³ (range 3,353-21,132 m³)OctNov 2025: 134 h spilling ≈ 83,058 m³ (range 33,084-208,521 m³)NovDec 2025: 282 h spilling ≈ 174,719 m³ (range 69,594-438,639 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 17:15Malvern Sewage Treatment Works3.2 days19,073 - 120,213 m³
15 Dec 2025, 12:35Malvern Sewage Treatment Works1.5 days8,711 - 54,901 m³
5 Jan 2025, 12:31Malvern Sewage Treatment Works1.5 days8,682 - 54,720 m³
8 Dec 2025, 23:38Malvern Sewage Treatment Works1.3 days7,683 - 48,427 m³
15 Nov 2025, 23:38Malvern Sewage Treatment Works1.1 days6,426 - 40,503 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate513,203 m³range 204,419 - 1.3 million m³
In litres513.2 millionrange 204.4 million - 1.3 billion L
Olympic swimming pools205at 2,500 m³ each
Organic load, as people's raw sewage769,804person-days of untreated BOD

Assumed spill rate while spilling: 68.5 - 431.6 L/s (central 171.9 L/s), from a dry-weather flow of 68.5 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 8,177 kg46,188 kg257,683 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 21,464 kg218,111 kg928,947 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 388 kg3,233 kg11,982 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 245 kg1,334 kg6,957 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 20.4 trillion organisms513.2 trillion organisms1.3 × 10¹⁶ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Malvern Sewage Treatment Works

Storm tank at sewage works · discharges to River Severn

Spills 2025
57 (637 hours) · down 61% on 2024
Spills 2024
148 (2,237 hours)
Long-term average
93.6 spills a year (monitored since 2021)
Monitor uptime
99% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Severn - conf R Teme to conf R Avon (GB109054039760)
Outlet location
SO8366045370 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00180 · S/08/26522/R · company name: MALVERN STW (SSTO)

Malvern Sewage Treatment Works

Inlet overflow at sewage works · discharges to River Severn

Spills 2025
33 (162 hours) · down 54% on 2024
Spills 2024
71 (376 hours)
Long-term average
45.2 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement ongoing
WFD catchment
Severn - conf R Teme to conf R Avon (GB109054039760)
Outlet location
SO8366045370 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00181 · S/08/26522/R · company name: MALVERN STW INLET WORKS 6 DWF (CSO)

Malvern Sewage Treatment Works

Inlet overflow at sewage works · discharges to Pool Brook

Spills 2025
13 (30 hours) · up 8% on 2024
Spills 2024
12 (10 hours)
Long-term average
12.5 spills a year (monitored since 2024)
Monitor uptime
100% of the year
Investigation
Operational investigation completed
Improvement
No improvement action in reporting period
WFD catchment
Pool Brook - source to conf R Severn (GB109054039720)
Outlet location
SO7975044930 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT00182 · Unpermitted · company name: BARNARDS GREEN LANE (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.