Storm overflow register · Severn Trent Water

Norton Green sewage works: storm overflow spills 2025

Norton Green sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Grand Union Canal Stream. In 2025 it recorded 30 spills totalling 325 hours, against 69 spills and 903 hours in 2024. By hours spilling, it ranks 122 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 10,226 population equivalent (NORTON GREEN STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecNorton Green STW5 Jan 2025 15:46 GMT, 55.8 h27 Jan 2025 02:16 GMT, 3.8 h27 Jan 2025 08:05 GMT, 2.1 h23 Feb 2025 22:45 GMT, 17.6 h24 Feb 2025 16:40 GMT, 33 min24 Feb 2025 17:16 GMT, 19 min24 Feb 2025 17:55 GMT, 3.7 h23 Apr 2025 04:01 GMT, 4.1 h4 Sep 2025 12:46 GMT, 80 min14 Sep 2025 17:16 GMT, 3.4 h19 Oct 2025 20:16 GMT, 2.2 h4 Nov 2025 21:17 GMT, 3.2 h5 Nov 2025 00:32 GMT, 16 min12 Nov 2025 09:16 GMT, 12.2 h12 Nov 2025 21:34 GMT, 18 min14 Nov 2025 08:31 GMT, 40.3 h16 Nov 2025 01:10 GMT, 14 min22 Nov 2025 13:46 GMT, 12.1 h23 Nov 2025 05:17 GMT, 11.3 h23 Nov 2025 16:55 GMT, 2.2 h23 Nov 2025 19:17 GMT, 77 min29 Nov 2025 08:46 GMT, 13.6 h29 Nov 2025 23:07 GMT, 12 min1 Dec 2025 13:25 GMT, 40 min1 Dec 2025 14:25 GMT, 35 min1 Dec 2025 19:01 GMT, 17 h6 Dec 2025 11:02 GMT, 8.1 h6 Dec 2025 19:25 GMT, 28 min9 Dec 2025 06:16 GMT, 21.1 h10 Dec 2025 03:40 GMT, 17 min10 Dec 2025 04:04 GMT, 31 min10 Dec 2025 07:36 GMT, 2.3 h15 Dec 2025 16:46 GMT, 32 h18 Dec 2025 00:16 GMT, 50.3 h

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

020k40k60kJan 2025: 62 h spilling ≈ 10,811 m³ (range 4,306–27,141 m³)JanFeb 2025: 22 h spilling ≈ 3,872 m³ (range 1,542–9,722 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 4.0 h spilling ≈ 701 m³ (range 279–1,760 m³)AprMay 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 4.7 h spilling ≈ 824 m³ (range 328–2,067 m³)SepOct 2025: 2.2 h spilling ≈ 385 m³ (range 154–968 m³)OctNov 2025: 97 h spilling ≈ 17,014 m³ (range 6,777–42,713 m³)NovDec 2025: 133 h spilling ≈ 23,339 m³ (range 9,296–58,593 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
5 Jan 2025, 15:46Norton Green STW2.3 days3,896 – 24,553 m³
18 Dec 2025, 00:16Norton Green STW2.1 days3,512 – 22,134 m³
14 Nov 2025, 08:31Norton Green STW1.7 days2,814 – 17,735 m³
15 Dec 2025, 16:46Norton Green STW1.3 days2,230 – 14,054 m³
9 Dec 2025, 06:16Norton Green STW21.1 h1,470 – 9,267 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate56,928 m³range 22,676 – 142,920 m³
In litres56.9 millionrange 22.7 million – 142.9 million L
Olympic swimming pools23at 2,500 m³ each
Organic load, as people's raw sewage85,392person-days of untreated BOD

Assumed spill rate while spilling: 19.4 – 122.2 L/s (central 48.7 L/s), from a dry-weather flow of 19.4 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 907 kg5,124 kg28,584 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,381 kg24,194 kg103,045 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 43 kg359 kg1,329 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 27 kg148 kg772 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.3 trillion organisms56.9 trillion organisms1.4 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Norton Green STW

Storm tank at sewage works · discharges to Grand Union Canal Stream

Spills 2025
30 (325 hours) · down 57% on 2024
Spills 2024
69 (903 hours)
Long-term average
60.2 spills a year (monitored since 2021)
Monitor uptime
100% of the year
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Cuttle Brook from Source to River Blythe (GB104028042390)
Outlet location
SP1860074700 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01677 · T/11/35235/R · company name: NORTON GREEN STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.