Storm overflow register · Severn Trent Water

Prees Higher Heath sewage works: storm overflow spills 2025

Prees Higher Heath sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Trib of Bailey Brook. In 2025 it recorded 15 spills totalling 90 hours, against 22 spills and 93 hours in 2024. By hours spilling, it ranks 272 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 2,051 population equivalent (PREES HIGHER HEATH STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecPrees - Higher Heath…1 Jan 2025 01:29 GMT, 1 min1 Jan 2025 02:14 GMT, 32 min1 Jan 2025 06:04 GMT, 42 min1 Jan 2025 07:43 GMT, 17 min1 Jan 2025 08:43 GMT, 2 min1 Jan 2025 09:14 GMT, 2 min1 Jan 2025 11:44 GMT, 2 min1 Jan 2025 12:44 GMT, 2 min5 Jan 2025 11:11 GMT, 26 min5 Jan 2025 11:52 GMT, 91 min5 Jan 2025 13:36 GMT, 32 min5 Jan 2025 14:21 GMT, 2.3 h5 Jan 2025 16:50 GMT, 107 min5 Jan 2025 18:51 GMT, 5.3 h6 Jan 2025 00:21 GMT, 4.2 h6 Jan 2025 04:59 GMT, 41 min6 Jan 2025 06:14 GMT, 2 min6 Jan 2025 06:44 GMT, 12 min6 Jan 2025 07:05 GMT, 109 min6 Jan 2025 10:44 GMT, 17 min6 Jan 2025 11:44 GMT, 2 min6 Jan 2025 12:44 GMT, 17 min6 Jan 2025 13:59 GMT, 17 min6 Jan 2025 15:29 GMT, 2 min6 Jan 2025 19:59 GMT, 16 min6 Jan 2025 20:44 GMT, 2 min7 Jan 2025 02:14 GMT, 1 min27 Jan 2025 02:59 GMT, 2 min27 Jan 2025 03:44 GMT, 77 min27 Jan 2025 06:14 GMT, 26 min27 May 2025 17:48 GMT, 17 min20 Sep 2025 13:50 GMT, 10.3 h21 Sep 2025 00:39 GMT, 30 min14 Nov 2025 09:56 GMT, 89 min14 Nov 2025 11:34 GMT, 34 min14 Nov 2025 12:31 GMT, 14 min14 Nov 2025 13:34 GMT, 16.7 h15 Nov 2025 06:30 GMT, 38 min15 Nov 2025 07:24 GMT, 4.3 h15 Nov 2025 12:08 GMT, 33 min29 Nov 2025 05:33 GMT, 4.4 h1 Dec 2025 21:18 GMT, 17 min9 Dec 2025 06:40 GMT, 7.3 h9 Dec 2025 14:14 GMT, 16 min15 Dec 2025 07:59 GMT, 11.5 h17 Dec 2025 20:39 GMT, 3.5 h18 Dec 2025 00:14 GMT, 11 min18 Dec 2025 00:54 GMT, 12 min18 Dec 2025 14:04 GMT, 2.8 h18 Dec 2025 17:09 GMT, 17 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

01,0002,0003,000Jan 2025: 23 h spilling ≈ 822 m³ (range 328–2,065 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)MarApr 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AprMay 2025: 0.3 h spilling ≈ 11 m³ (range 4.2–26 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)AugSep 2025: 11 h spilling ≈ 380 m³ (range 151–953 m³)SepOct 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)OctNov 2025: 29 h spilling ≈ 1,012 m³ (range 403–2,541 m³)NovDec 2025: 26 h spilling ≈ 924 m³ (range 368–2,320 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 13:34Prees - Higher Heath STW16.7 h234 – 1,472 m³
15 Dec 2025, 07:59Prees - Higher Heath STW11.5 h161 – 1,012 m³
20 Sep 2025, 13:50Prees - Higher Heath STW10.3 h145 – 912 m³
9 Dec 2025, 06:40Prees - Higher Heath STW7.3 h102 – 641 m³
5 Jan 2025, 18:51Prees - Higher Heath STW5.3 h74 – 465 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate3,149 m³range 1,254 – 7,905 m³
In litres3.1 millionrange 1.3 million – 7.9 million L
Olympic swimming pools1.3at 2,500 m³ each
Organic load, as people's raw sewage4,723person-days of untreated BOD

Assumed spill rate while spilling: 3.9 – 24.5 L/s (central 9.8 L/s), from a dry-weather flow of 3.9 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 50 kg283 kg1,581 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 132 kg1,338 kg5,700 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 2.4 kg20 kg74 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 1.5 kg8.2 kg43 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 125.4 billion organisms3.1 trillion organisms79.1 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Prees - Higher Heath STW

Storm tank at sewage works · discharges to Trib of Bailey Brook

Spills 2025
15 (90 hours) · down 32% on 2024
Spills 2024
22 (93 hours)
Long-term average
23.0 spills a year (monitored since 2021)
Monitor uptime
99% of the year
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing, Operational investigation completed
Improvement
UWWTR improvement ongoing, Operational improvement completed
WFD catchment
Bailey Bk - source to conf R Tern (GB109054055140)
Outlet location
SJ5735135166 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01821 · S/04/56056/R · company name: PREES - HIGHER HEATH STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.