Storm overflow register · Severn Trent Water

Ravenstone sewage works: storm overflow spills 2025

Ravenstone sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to Tributary of Blower'S Brook. In 2025 it recorded 34 spills totalling 168 hours, against 104 spills and 654 hours in 2024. By hours spilling, it ranks 199 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 2,228 population equivalent (RAVENSTONE STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecRavenstone Sewage…6 spills, 19.8 h, 5 Jan to 6 Jan27 Jan 2025 01:34 GMT, 50 min23 Apr 2025 03:17 GMT, 2.9 h2 spills, 5.4 h, 27 May to 27 May7 Jun 2025 16:01 GMT, 110 min3 spills, 3.1 h, 6 Jul to 7 Jul20 Jul 2025 18:51 GMT, 33 min10 Sep 2025 19:17 GMT, 40 min14 Sep 2025 15:46 GMT, 4.9 h2 spills, 1.5 h, 17 Sep to 17 Sep2 spills, 3.1 h, 20 Sep to 21 Sep2 spills, 3.4 h, 3 Oct to 3 Oct19 Oct 2025 22:04 GMT, 33 min1 Nov 2025 01:17 GMT, 51 min4 Nov 2025 18:30 GMT, 3.3 h4 spills, 6.2 h, 10 Nov to 10 Nov2 spills, 1.5 h, 12 Nov to 12 Nov9 spills, 41.4 h, 14 Nov to 16 Nov8 spills, 12.8 h, 22 Nov to 23 Nov2 spills, 6.6 h, 29 Nov to 29 Nov5 Dec 2025 19:07 GMT, 39 min7 spills, 3.9 h, 9 Dec to 9 Dec2 spills, 0.4 h, 12 Dec to 12 Dec7 spills, 7.4 h, 16 Dec to 16 Dec10 spills, 29.3 h, 18 Dec to 19 Dec3 spills, 5.4 h, 21 Dec to 22 Dec

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low-high range. Method.

02,0004,0006,0008,000Jan 2025: 21 h spilling ≈ 786 m³ (range 313-1,974 m³)JanFeb 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)FebMar 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)MarApr 2025: 2.9 h spilling ≈ 111 m³ (range 44-278 m³)AprMay 2025: 5.4 h spilling ≈ 206 m³ (range 82-518 m³)MayJun 2025: 1.8 h spilling ≈ 69 m³ (range 27-173 m³)JunJul 2025: 3.7 h spilling ≈ 141 m³ (range 56-355 m³)JulAug 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0-0.0 m³)AugSep 2025: 10 h spilling ≈ 389 m³ (range 155-978 m³)SepOct 2025: 4.0 h spilling ≈ 153 m³ (range 61-383 m³)OctNov 2025: 73 h spilling ≈ 2,768 m³ (range 1,102-6,948 m³)NovDec 2025: 47 h spilling ≈ 1,798 m³ (range 716-4,514 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 07:17Ravenstone Sewage Treatment Works1.6 days599 - 3,778 m³
18 Dec 2025, 13:03Ravenstone Sewage Treatment Works1.0 days382 - 2,407 m³
6 Jan 2025, 01:56Ravenstone Sewage Treatment Works14.5 h220 - 1,385 m³
23 Nov 2025, 05:32Ravenstone Sewage Treatment Works7.1 h107 - 676 m³
29 Nov 2025, 08:05Ravenstone Sewage Treatment Works6.4 h98 - 617 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate6,421 m³range 2,558 - 16,120 m³
In litres6.4 millionrange 2.6 million - 16.1 million L
Olympic swimming pools2.6at 2,500 m³ each
Organic load, as people's raw sewage9,632person-days of untreated BOD

Assumed spill rate while spilling: 4.2 - 26.6 L/s (central 10.6 L/s), from a dry-weather flow of 4.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 102 kg578 kg3,224 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 269 kg2,729 kg11,623 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 4.9 kg40 kg150 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3-9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 3.1 kg17 kg87 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 255.8 billion organisms6.4 trillion organisms161.2 trillion organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Ravenstone Sewage Treatment Works

Storm tank at sewage works · discharges to Tributary of Blower'S Brook

Spills 2025
34 (168 hours) · down 67% on 2024
Spills 2024
104 (654 hours)
Long-term average
89.4 spills a year (monitored since 2021)
Monitor uptime
100% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation completed, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Sence from Source to Ibstock Brook (GB104028046750)
Outlet location
SK3955213136 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT01869 · T/20/35618/R · company name: RAVENSTONE STW (SSTO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024-25 [EA]. Infiltration of groundwater into sewers is taken as 0-40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies - environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 - per capita consumption
  3. HBF: Foul sewer design - historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 - CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.