Storm overflow register · Severn Trent Water

Skegby sewage works: storm overflow spills 2025

Skegby sewage treatment works, run by Severn Trent Water, has 2 monitored storm overflows discharging to Skegby Brook. In 2025 they recorded 75 spills totalling 367 hours, against 123 spills and 627 hours in 2024. By hours spilling, it ranks 112 of 435 Severn Trent Water works, where 1 spilled longest.

Works size: 11,201 population equivalent (SKEGBY STW, UWWTD 2018). Used for the spill volume estimate.

Every spill in 2025

Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.

JanFebMarAprMayJunJulAugSepOctNovDecSkegby Sewage…1 Jan 2025 00:00 GMT, 2.2 h1 Jan 2025 03:16 GMT, 27 min1 Jan 2025 05:17 GMT, 5.3 h1 Jan 2025 18:47 GMT, 40 min5 Jan 2025 08:33 GMT, 39.4 h27 Jan 2025 01:40 GMT, 2.9 h27 Jan 2025 21:15 GMT, 2.1 h28 Jan 2025 07:49 GMT, 39 min22 Mar 2025 20:16 GMT, 38 min28 May 2025 03:15 GMT, 86 min28 May 2025 05:32 GMT, 48 min17 Sep 2025 06:00 GMT, 4.7 h20 Sep 2025 20:30 GMT, 60 min20 Sep 2025 21:30 GMT, 99 min20 Sep 2025 23:15 GMT, 2.7 h19 Oct 2025 21:00 GMT, 96 min4 Nov 2025 19:45 GMT, 3.4 h10 Nov 2025 15:30 GMT, 118 min11 Nov 2025 22:15 GMT, 2.4 h14 Nov 2025 05:45 GMT, 48.6 h16 Nov 2025 06:40 GMT, 10 min16 Nov 2025 07:10 GMT, 10 min16 Nov 2025 07:40 GMT, 10 min16 Nov 2025 08:10 GMT, 12.2 h16 Nov 2025 20:40 GMT, 25 min18 Nov 2025 16:15 GMT, 87 min18 Nov 2025 18:03 GMT, 54 min23 Nov 2025 06:32 GMT, 4.5 h23 Nov 2025 13:36 GMT, 2.9 h29 Nov 2025 04:30 GMT, 14.8 h29 Nov 2025 19:40 GMT, 19 min29 Nov 2025 20:51 GMT, 3.5 h1 Dec 2025 07:35 GMT, 7 h1 Dec 2025 19:40 GMT, 3.7 h4 Dec 2025 16:48 GMT, 2 h4 Dec 2025 19:10 GMT, 10 min4 Dec 2025 19:40 GMT, 2.6 h5 Dec 2025 18:30 GMT, 6.7 h9 Dec 2025 04:30 GMT, 18.1 h9 Dec 2025 22:55 GMT, 42 min15 Dec 2025 17:16 GMT, 5.8 h15 Dec 2025 23:51 GMT, 89 min16 Dec 2025 01:40 GMT, 2.2 h16 Dec 2025 04:25 GMT, 7.8 h17 Dec 2025 23:30 GMT, 2.1 h18 Dec 2025 14:00 GMT, 13.1 h19 Dec 2025 07:01 GMT, 6.8 h19 Dec 2025 18:17 GMT, 37 min21 Dec 2025 21:30 GMT, 5.5 h22 Dec 2025 10:53 GMT, 12 min22 Dec 2025 12:07 GMT, 13 min22 Dec 2025 13:10 GMT, 10 min22 Dec 2025 16:32 GMT, 18 minSkegby Sewage…1 Jan 2025 00:00 GMT, 43 min1 Jan 2025 05:47 GMT, 2.6 h5 Jan 2025 16:01 GMT, 3.1 h5 Jan 2025 19:34 GMT, 31 min5 Jan 2025 20:25 GMT, 19.4 h24 Jan 2025 03:21 GMT, 37 min24 Jan 2025 04:02 GMT, 36 min26 Jan 2025 14:47 GMT, 64 min27 Jan 2025 01:10 GMT, 2.5 h27 Jan 2025 20:31 GMT, 2.1 h23 Feb 2025 14:25 GMT, 17 min22 Mar 2025 15:46 GMT, 64 min22 Mar 2025 20:02 GMT, 34 min15 Apr 2025 23:50 GMT, 34 min24 May 2025 00:33 GMT, 64 min28 May 2025 02:46 GMT, 42 min30 Aug 2025 20:48 GMT, 34 min3 Sep 2025 14:05 GMT, 52 min4 Sep 2025 11:00 GMT, 43 min4 Sep 2025 12:31 GMT, 32 min14 Sep 2025 15:03 GMT, 66 min17 Sep 2025 05:18 GMT, 97 min17 Sep 2025 07:15 GMT, 38 min20 Sep 2025 19:15 GMT, 116 min20 Sep 2025 23:17 GMT, 114 min3 Oct 2025 14:32 GMT, 70 min19 Oct 2025 19:18 GMT, 17 min19 Oct 2025 20:35 GMT, 65 min31 Oct 2025 14:01 GMT, 40 min4 Nov 2025 18:41 GMT, 2 h10 Nov 2025 04:01 GMT, 60 min10 Nov 2025 12:31 GMT, 36 min10 Nov 2025 15:17 GMT, 53 min11 Nov 2025 22:01 GMT, 94 min14 Nov 2025 05:13 GMT, 5 min14 Nov 2025 06:04 GMT, 9.4 h14 Nov 2025 15:45 GMT, 15.8 h15 Nov 2025 07:55 GMT, 14 min15 Nov 2025 10:25 GMT, 19 min18 Nov 2025 16:05 GMT, 54 min23 Nov 2025 05:32 GMT, 40 min29 Nov 2025 03:49 GMT, 23 min29 Nov 2025 04:16 GMT, 2.1 h29 Nov 2025 18:03 GMT, 2.6 h29 Nov 2025 21:00 GMT, 56 min1 Dec 2025 02:33 GMT, 23 min1 Dec 2025 03:03 GMT, 23 min1 Dec 2025 04:02 GMT, 54 min1 Dec 2025 05:03 GMT, 39 min1 Dec 2025 19:18 GMT, 51 min5 Dec 2025 17:45 GMT, 89 min5 Dec 2025 19:48 GMT, 68 min5 Dec 2025 21:18 GMT, 68 min5 Dec 2025 22:33 GMT, 23 min5 Dec 2025 23:03 GMT, 23 min5 Dec 2025 23:48 GMT, 38 min6 Dec 2025 01:03 GMT, 23 min9 Dec 2025 03:33 GMT, 2.8 h9 Dec 2025 07:25 GMT, 24 min9 Dec 2025 08:48 GMT, 23 min9 Dec 2025 09:18 GMT, 53 min9 Dec 2025 10:52 GMT, 33 min15 Dec 2025 19:17 GMT, 68 min16 Dec 2025 06:03 GMT, 38 min17 Dec 2025 21:18 GMT, 23 min17 Dec 2025 22:33 GMT, 39 min17 Dec 2025 23:30 GMT, 24 min18 Dec 2025 13:33 GMT, 3.6 h18 Dec 2025 17:18 GMT, 69 min18 Dec 2025 19:18 GMT, 23 min18 Dec 2025 20:01 GMT, 26 min18 Dec 2025 20:32 GMT, 26 min21 Dec 2025 21:41 GMT, 44 min

Estimated spill volume by month, 2025

Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.

020k40k60k80kJan 2025: 87 h spilling ≈ 16,678 m³ (range 6,643–41,871 m³)JanFeb 2025: 0.3 h spilling ≈ 58 m³ (range 23–145 m³)FebMar 2025: 2.2 h spilling ≈ 422 m³ (range 168–1,060 m³)MarApr 2025: 0.6 h spilling ≈ 115 m³ (range 46–289 m³)AprMay 2025: 4.0 h spilling ≈ 768 m³ (range 306–1,927 m³)MayJun 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JunJul 2025: 0.0 h spilling ≈ 0.0 m³ (range 0.0–0.0 m³)JulAug 2025: 0.6 h spilling ≈ 115 m³ (range 46–289 m³)AugSep 2025: 19 h spilling ≈ 3,704 m³ (range 1,475–9,299 m³)SepOct 2025: 4.8 h spilling ≈ 921 m³ (range 367–2,313 m³)OctNov 2025: 137 h spilling ≈ 26,351 m³ (range 10,496–66,155 m³)NovDec 2025: 111 h spilling ≈ 21,246 m³ (range 8,463–53,339 m³)Dec
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.

Longest single spills

Started (GMT)OverflowDurationEstimated volume
14 Nov 2025, 05:45Skegby Sewage Treatment Works2.0 days3,713 – 23,401 m³
5 Jan 2025, 08:33Skegby Sewage Treatment Works1.6 days3,013 – 18,992 m³
5 Jan 2025, 20:25Skegby Sewage Treatment Works19.4 h1,484 – 9,356 m³
9 Dec 2025, 04:30Skegby Sewage Treatment Works18.1 h1,381 – 8,705 m³
14 Nov 2025, 15:45Skegby Sewage Treatment Works15.8 h1,209 – 7,621 m³

Estimated 2025 spill volume and pollution

Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.

Volume, central estimate70,378 m³range 28,033 – 176,687 m³
In litres70.4 millionrange 28.0 million – 176.7 million L
Olympic swimming pools28at 2,500 m³ each
Organic load, as people's raw sewage105,567person-days of untreated BOD

Assumed spill rate while spilling: 21.2 – 133.8 L/s (central 53.3 L/s), from a dry-weather flow of 21.2 L/s.

Pollutant releasedLowCentralHighConcentration used (low / typical / high)
BOD₅ (organic load) 1,121 kg6,334 kg35,337 kg 40 / 90 / 200 mg/L
Low/high: Europe range, Ellis & Jenkins 2005; typical: UK, Ellis & Jenkins 2005 (both via botturi)
Suspended solids 2,943 kg29,911 kg127,391 kg 105 / 425 / 721 mg/L
Low/high: Europe range; typical: UK, Ellis & Jenkins 2005 (via botturi)
Ammonium-N 53 kg443 kg1,643 kg 1.9 / 6.3 / 9.3 mg/L
Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus 34 kg183 kg954 kg 1.2 / 2.6 / 5.4 mg/L
Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli 2.8 trillion organisms70.4 trillion organisms1.8 × 10¹⁵ organisms 10,000 / 100,000 / 1.0 million per 100 mL
Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint

Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.

Skegby Sewage Treatment Works

Storm tank at sewage works · discharges to Skegby Brook

Spills 2025
37 (253 hours) · down 39% on 2024
Spills 2024
61 (420 hours)
Long-term average
52.2 spills a year (monitored since 2021)
Monitor uptime
98% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
Env Act (SODRP) investigation ongoing, UWWTR investigation ongoing, Operational investigation completed
Improvement
Operational improvement completed
WFD catchment
Meden from Source to Sookholme Brook (GB104028058020)
Outlet location
SK4969461467 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT02059 · T/71/45942/R · company name: SKEGBY STW (SSTO)

Skegby Sewage Treatment Works

Inlet overflow at sewage works · discharges to Skegby Brook

Spills 2025
38 (114 hours) · down 39% on 2024
Spills 2024
62 (208 hours)
Long-term average
74.4 spills a year (monitored since 2021)
Monitor uptime
99% of the year
High-spill reason (company)
Not asset maintenance - Hydraulic capacity
Investigation
UWWTR investigation ongoing, Operational investigation completed
Improvement
UWWTR improvement completed
WFD catchment
Meden from Source to Sookholme Brook (GB104028058020)
Outlet location
SK4969461467 (OS grid reference) · View on Apple Maps
EA ID / permit
SVT02058 · T/71/45942/R · company name: SKEGBY STW (CSO)

How the estimate works

  1. Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
  2. Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
  3. Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
  4. High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
  5. Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
  6. Pollution = volume × published storm-sewage concentrations [Botturi et al.] [US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].

What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.

Sources

  1. EA: Water companies – environmental permits for storm overflows and emergency overflows
  2. EA: Water resources 2024 to 2025 – per capita consumption
  3. HBF: Foul sewer design – historic conventions (citing Escritt 1984 on infiltration)
  4. Giakoumis & Voulvoulis (2026), Environ. Sci.: Water Res. Technol., doi:10.1039/D5EW00860C
  5. Botturi et al. (2021), Crit. Rev. Environ. Sci. Technol. 51:1585 – CSO quality review, Table 2
  6. US EPA (2004) Report to Congress on CSOs and SSOs, chapter 4
  7. Urban Waste Water Treatment Directive, Article 2(6): 1 p.e. = 60 g BOD5/day
  8. Olympic-size swimming pool: 2,500 m³ at the nominal 2 m depth

← All Severn Trent Water works · Contains Environment Agency data licensed under the Open Government Licence v3.0. Spill start and stop times: © Environment Agency copyright and/or database right 2026. All rights reserved. They are water-company data and have not been verified by the Environment Agency. Works size: EEA Waterbase UWWTD. How to read the data.