Winchcombe sewage treatment works, run by Severn Trent Water, has 1 monitored storm overflow discharging to River Isbourne. In 2025 it recorded 29 spills totalling 142 hours, against 56 spills and 421 hours in 2024. By hours spilling, it ranks 221 of 435 Severn Trent Water works, where 1 spilled longest.
Works size: 4,694 population equivalent (WINCHCOMBE STW, UWWTD 2018). Used for the spill volume estimate.
Every spill in 2025
Each blue mark is one spill, placed by when it started and sized by how long it lasted. Hover over a mark for the date and duration.
Estimated spill volume by month, 2025
Hours spilling each month × the estimated spill rate for a works of this size. The bars are central estimates and the whiskers show the low–high range. Method.
Cubic metres (m³), estimate. Hours are measured by the event duration monitor.
Longest single spills
Started (GMT)
Overflow
Duration
Estimated volume
26 Jan 2025, 21:52
Winchcombe Sewage Treatment Works
12.9 h
412 – 2,595 m³
28 Jan 2025, 04:19
Winchcombe Sewage Treatment Works
8.6 h
275 – 1,733 m³
6 Jan 2025, 15:21
Winchcombe Sewage Treatment Works
6.6 h
210 – 1,326 m³
16 Dec 2025, 04:52
Winchcombe Sewage Treatment Works
6.0 h
192 – 1,212 m³
27 Jan 2025, 19:49
Winchcombe Sewage Treatment Works
5.6 h
179 – 1,127 m³
Estimated 2025 spill volume and pollution
Estimate, not a measurement. Monitors record how long an overflow spills, not how much. This calculator back-calculates a spill rate from the size of the works, using the Environment Agency's permit formulae, and multiplies it by published storm-sewage concentrations. How it works.
Volume, central estimate11,421 m³range 4,549 – 28,673 m³
In litres11.4 millionrange 4.5 million – 28.7 million L
Olympic swimming pools4.6at 2,500 m³ each
Organic load, as people's raw sewage17,131person-days of untreated BOD
Assumed spill rate while spilling: 8.9 – 56.1 L/s (central 22.3 L/s), from a dry-weather flow of 8.9 L/s.
1.9 / 6.3 / 9.3 mg/L Low: Germany, Brombach 2005; typical/high: Paris range 3.3–9.3 midpoint and top, Gasperi 2012 (via botturi); no UK value found
Total phosphorus
5.5 kg
30 kg
155 kg
1.2 / 2.6 / 5.4 mg/L Low/high: Paris, Gasperi 2012; typical: Slovakia (via botturi). UK figure of 10 mg/L treated as an outlier
E. coli
454.9 billion organisms
11.4 trillion organisms
286.7 trillion organisms
10,000 / 100,000 / 1.0 million per 100 mL Median range at CSO and retention-tank outlets, Stott et al. 2018 (via botturi); typical = log midpoint
Low combines the low spill rate with low concentrations, and high combines high with high, so the true figure is very likely inside the range. Long spills become more diluted as they go on, so the central figure tends to overstate the load of long events. The calculator does not estimate the effect on the receiving water, which depends on river flow or tide at the time of the spill.
Winchcombe Sewage Treatment Works
Storm tank at sewage works · discharges to River Isbourne
Spills 2025
29 (142 hours) · down 48% on 2024
Spills 2024
56 (421 hours)
Long-term average
38.0 spills a year (monitored since 2020)
Monitor uptime
88% of the year · Telemetry or data archiving failure / issue
SVT02571 · S/18/26092/R · company name: WINCHCOMBE (STW)
How the estimate works
Dry-weather flow (DWF) = population × water use per person × (1 + infiltration). Water use is 136.5 L per person per day, England's per-capita consumption for 2024–25 [EA]. Infiltration of groundwater into sewers is taken as 0–40% of that flow [Escritt, via HBF]. The Environment Agency defines DWF as PG + I + E [EA].
Population. The size of each works comes from the load entering it as reported under the Urban Waste Water Treatment Directive, in population equivalents (1 p.e. = 60 g of BOD a day) [UWWTD]. We treat population equivalent as population. That overstates flow where trade effluent adds load, and no official source links the two. Works serving fewer than 2,000 p.e. are not reported, so their size has to be entered by hand.
Low spill rate = DWF. This is the method used by Giakoumis & Voulvoulis (2026), which they note likely underestimates storm loads [G&V].
High spill rate = Formula A − flow to full treatment = (DWF + 1360P) − 3DWF. This is the largest flow the permit expects the storm tanks to handle before it passes on to treatment or overflows [EA]. The central rate is the geometric mean of the low and high rates.
Volume = spill rate × hours spilling, with hours taken from the event duration monitor.
Pollution = volume × published storm-sewage concentrations [Botturi et al.][US EPA]. Organic load is also shown as person-days of untreated sewage at 60 g of BOD per person per day [UWWTD].
What this cannot tell you. It gives no real flow for any single spill, and no effect on the river or sea, which depends on the flow, tide and the other pressures on the water at the time. It gives no figure for spills from overflows on the sewer network, which serve catchments of unknown size. It is a way to put hours into rough physical terms, not a substitute for flow monitoring.